Two Stage Acceleration and Deceleration 
When terminal [2CH] is turned ON, the inverter 
changes the rate of acceleration and 
deceleration from the initial settings (
F002
 and 
F003
) to use the second set of acceleration/ 
deceleration values. When the terminal is 
turned OFF, the inverter is returned to the 
original acceleration and deceleration time 
(
F002
 acceleration time 1, and 
F003
 
deceleration time 1). Use 
A092
 (acceleration 
time 2) and 
A093
 (deceleration time 2) to set 
the second stage acceleration and deceleration 
times. 
In the graph shown above, the [2CH] becomes active during the initial acceleration. This 
causes the inverter to switch from using acceleration 1 (
F002
) to acceleration 2 (
A092
). 
 
Option 
Code 
Terminal 
Symbol 
Function Name 
State
Description 
ON 
Frequency output uses 2nd-stage acceleration and 
deceleration values 
09 
2CH Two-stage 
Accelera-
tion and 
Deceleration 
OFF
Frequency output uses the initial acceleration 1 and 
deceleration 1 values 
Valid for inputs: 
C001
~
C007
 
Required settings 
A092
A093
A094
=
00
 
Notes: 
•  Function 
A094
 selects the method for second 
stage acceleration. It must be set = 
00
 to select 
the input terminal method in order for the [2CH] 
terminal assignment to operate. 
Example (default input configuration shown see 
page 66
): 
 
 
 
 
 
 
 
See I/O specs on 
page 21,22.
 
 
 
[2CH] 
1
0
Output 
frequency 
t
[FW,RV]
1
0
Target 
frequency 
initial 
second 
2CH
7
6
5
4
3
2
 
1
 
L
 
P24
 
PLC