Alarm Signal 
The inverter alarm signal is active when a fault has 
occurred and it is in the Trip Mode (refer to the 
diagram at right). When the fault is cleared the alarm 
signal becomes inactive. 
We must make a distinction between the alarm signal 
AL and the alarm relay contacts [AL0], [AL1] and [AL2]. 
The signal AL is a logic function, which you can assign 
to the open collector output terminals [11], [12], or the 
relay outputs.   
The most common (and default) use of the relay is for AL, thus the labeling of its terminals. 
Use an open collector output (terminal [11] or [12]) for a low-current logic signal interface 
or to energize a small relay (50 mA maximum). Use the relay output to interface to higher 
voltage and current devices (10 mA minimum). 
Option 
Code 
Terminal 
Symbol 
Function Name 
State
Description 
ON 
when an alarm signal has occurred and has not 
been cleared 
05 
AL Alarm 
Signal 
OFF
when no alarm has occurred since the last clearing 
of alarm(s) 
Valid for inputs: 
11, 12, AL0 – AL2 
Required settings 
C031
C032
C036
 
Notes: 
•  By default, the relay is configured as normally 
closed (
C036
=
01
). Refer to the next page for an 
explanation. 
•  In the default relay configuration, an inverter 
power loss turns ON the alarm output. the alarm 
signal remains ON as long as the external control 
circuit has power. 
•  When the relay output is set to normally closed, a 
time delay of less than 2 seconds occurs after 
powerup before the contact is closed. 
•  Terminals [11] and [12] are open collector 
outputs, so the electric specifications of [AL] are 
different from the contact output terminals [AL0], 
[AL1], [AL2]. 
•  This signal output has the delay time (300 ms 
nominal) from the fault alarm output. 
•  The relay contact specifications are in “Control 
Logic Signal Specifications” on page 4–6. The 
contact diagrams for different conditions are on 
the next page. 
Example for terminal [11] (default output 
configuration shown see page 66): 
 
 
 
 
 
 
 
 
 
 
 
 
 
Example for terminal [AL0], [AL1], [AL2] (requires 
output configuration see page 66): 
 
 
 
 
 
 
 
 
 
 
 
 
See I/O specs on 
page 21,22.
 
 
 
Run
Stop 
RUN 
STOP 
RESET 
Trip 
STOP 
RESET 
Fault 
Fault 
Alarm signal active 
RY
Inverter output
terminal circuit
CM2
11
AL
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
AL