Hitachi hitachi series inverter 사용자 설명서

다운로드
페이지 99
 
37 
Frequency Arrival Signals 
The Frequency Arrival group of outputs helps coordinate external systems with the current 
velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output 
frequency arrives at the standard set frequency (parameter F001). Output [FA2] relies on 
programmable accel/ decel thresholds for increased flexibility. For example, you can have 
an output turn ON at one frequency during acceleration, and have it turn OFF at a different 
frequency during deceleration. All transitions have hysteresis to avoid output chatter if the 
output frequency is near one of the thresholds. 
Option 
Code 
Terminal 
Symbol 
Function Name 
State
Description 
ON  when output to motor is at the constant frequency 
01 
FA1 Frequency 
Arrival 
Type 1 – Constant 
Speed 
OFF  when output to motor is OFF, or in any acceleration or 
deceleration ramp 
ON  when output to motor is at or above the set frequency 
thresholds for, even if in acceleration or decel ramps 
02 
FA2 Frequency 
Arrival 
Type 2 – Over 
frequency 
OFF  when output to motor is OFF, or during accel or decel 
before the respective thresholds are crossed 
ON  when output to motor is at the set frequency 
06
 
FA3 Frequency 
Arrival 
Type 3 – Set 
frequency 
OFF  when output to motor is OFF, or in any acceleration or 
deceleration ramp 
ON  when output to motor is at or above the set frequency 
thresholds for, even if in acceleration or decel ramps 
24
 
FA4 Frequency 
Arrival 
Type 4 – Over 
frequency (2) 
OFF  when output to motor is OFF, or during accel or decel 
before the respective thresholds are crossed 
ON  when output to motor is at the set frequency 
25
 
FA5 Frequency 
Arrival 
Type 5 – Set 
frequency (2) 
OFF  when output to motor is OFF, or in any acceleration or 
deceleration ramp 
Valid for inputs: 
11, 12, AL0 – AL2 
Required 
settings 
C042
C043
C045
C046
Notes: 
•  For most applications you will need to use only 
one type of frequency arrival outputs (see 
examples). However, it is possible assign both 
output terminals to output functions [FA1] and 
[FA2] 
•  For each frequency arrival threshold, the output 
anticipates the threshold (turns ON early) by 
1.5Hz 
•  The output turns OFF as the output frequency 
moves away from the threshold, delayed by 
0.5Hz 
•  The example circuit for terminal [11] drives a 
relay coil. Note the use of a diode to prevent the 
negative going turn-off spike generated by the 
coil from damaging the inverter’s output 
transistor 
Example for terminal [11] (default output configuration 
shown see page 66): 
 
 
 
 
 
 
 
 
 
 
 
 
Example for terminal [AL0], [AL1], [AL2] (requires 
output configuration see 
page 66
): 
 
 
 
 
 
 
 
 
 
 
 
See I/O specs on 
page 21,22.
 
RY
Inverter output
terminal circuit
CM2
11
FA1
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
FA1