Functional Safety (Certification in Progress) 
Introduction 
The Gate Suppress function can be utilized to perform a safe stop according to the 
EN60204-1, stop category 0 (Uncontrolled stop by power removal). It is designed to meet 
the requirements of the ISO13849-1, PL=d only in a system in which EDM signal is 
monitored by an “external device monitor”. 
 
 
Stop Category defined in EN60204-1 
Category 0 : Uncontrolled stop by immediate (< 200 ms) shut-down of the power supply to 
the actuators 
Category 1 : Controlled stop by interrupting the power supply to the actuator level if, for 
example, the hazardous movement has been brought to a standstill 
(time-delayed shut-down of the power supply). 
Category 2 : Controlled stop. The power supply to the drive element is not interrupted. 
Additional measures to EN 1037 (protection from unexpected restart) are 
necessary. 
 
How it works 
Interrupting the current to GS1 or GS2, for 
example removing the link between either GS1 
or GS2 and PLC or both GS1/GS2 and PLC 
disables the drive output, i.e. the power supply 
to the motor is cut by stopping the switching of 
the output transistors in a safe way. EDM output 
is activated when GS1 and GS2 are given to the 
drive. 
Always use both inputs to disable the drive. If for 
any reason only one channel is opened, the 
drive output is stopped but the EDM output is 
not activated. In this case the Safe Disable input 
wiring must be checked. 
 
Activation 
Turning on the safety switch automatically 
assign the GS1 input and GS2 input 
automatically.  
To assign EDM (external device monitor) output, 
please turn the EDM function switch on. EDM 
output is automatically assigned on intelligent 
output terminal 11. 
Safety function 
switch 
EDM function 
switch
 
ON
OFF
ON 
(EDM) 
OFF 
(normal)