Wiring example 
When the Gate Suppress function is utilized, connect the drive to a safety certified 
interrupting device utilizing EDM output signal to reconfirm both safety inputs GS1 and 
GS2.  
 
 
 
 
 
 
 
 
 
 
 
 
 
By pressing the emergency stop button, the current to GS1 and GS2 is shut off, and the 
inverter output is shut off. By this, motor is free-running. This behavior is according to the 
stop category 0 defined in EN60204. 
Note 1: Above is the example to use the intelligent input terminal with source logic. When 
it is used with sink logic, the wiring is to be modified. 
Note 2: The wire for safety relay and emergency input signal are to be shielded coaxial 
cable for example RS174/U (produced by LAPP) by MIL-C17, or KX2B by NF C 
93-550 with diameter 2.9mm with less than 2 meters. Please be sure to ground 
the shielding. 
Note 3: All the inductance related parts such as relay and contactor are required to 
contain the over-voltage protection circuit.     
 
 
 
 
The arch extinguishing fuse with rated voltage AC250V, rated current 100mA complies 
to either IEC6127 –2/-3/-4 
Example) 
SOC  EQ series AC250V, 100mA (UL, SEMKO, BSI) 
Little  216 series AC250V, 100mA (CCC, UL, CSA, SEMKO, CE, VDE) 
EDM 
(feedback) input 
WJ200 
Safety output
Safety Unit 
Standard 
(IEC61508,ISO13849) 
certified 
KM1 
M
 
Reset  
Switch 
GS2
GS1
EDM
CM2
Safety input 
 
S14
S24
T12 
T21 
T22 
A1 
A2 
Safety Switch 
(Example: emergency   
push button) 
T11  T31
T32 
PLC 
+24V 
T33
+24V 
Fuse
G9SX-GS226-T15-RC