Inverter doesn’t block the current flowing into itself when it is not powered. 
This may cause 
the closed circuit when two or more inverters are connected to common I/O wiring as 
shown below to result in unexpected turning the on the input. This may lead to 
dangerous situation. To avoid this closed circuit, please put the diode (rated:50V/0.1A) 
in the path as described below. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   