GE LTC MAP 사용자 설명서
Section 1: Introduction
1-3
70055MP Revision D
February 3, 2000
Specifications
Input
Analog Seventeen (17) channels.
Channels 1 - 7
Input: 4 to 20 mA.
Sample rate: 150 Hz.
Channel 8
Input:
±
10 VDC.
Sample rate: 150 Hz.
Channels 9-11
Configurable input:
•
4 to 20 mA with a sample rate of 150 Hz, or
•
5A AC (as monitored by a CT) with a sample rate of 1920
Hz.
Channel 12
Configurable input:
•
4 to 20 mA with a sample rate of 150 Hz, or
•
50A AC (as monitored by a CT) with a sample rate of
1920 Hz.
Channels 13-16
Configurable input:
•
4 to 20 mA with a sample rate of 150 Hz, or
•
120/240 VAC with a sample rate of 1920 Hz.
Channel 17
Configurable input:
•
4 to 20 mA with a sample rate of 150 Hz, or
•
Signal conditioned with a sample rate of 1920 Hz.
Digital Sixteen channels via two optional control isolators (eight
channels each).
Input:
Input:
±
120/240 VAC.
Sample rate: 960z.