7.4  Positioning the Unit 
It is necessary to have a floor protection made of non-combustible materials that meets the 
measurements specified in table FLOOR PROTECTION (see Section 8.5). To determine 
the  need  to  add  floor  protection  (D)  beyond  the  hearth  extension,  you  must  do  the 
following calculation using the data in Table Data for floor protection calculation of this 
section: D = B - (A - C). If the value (D) is negative or zero, you do not have to add more 
floor protection in front of the unit, because the masonry fireplace hearth extension is large 
enough.  If  the  value  (D)  is  positive,  you  will  need  floor  protection  in  front  of  the  hearth 
extension at least equivalent to the result (D). 
Here  is  a  sample  calculation  to  determine  the  need  to  add  a  non-combustible  materials 
floor  protection.  For  someone  living  in  the  USA  whose  insert  would  protrude  3"  (76  mm) 
into the room (C) the calculation would be: 
 
Value D = B - (A - C) 
 
Value D = 16" - (16" - 3") 
 
Value D = 16" - 13" 
 
Value D = 3" 
Non-combustible floor protection of at least 3" (76 mm) in depth must be installed in front 
of the fireplace hearth extension.