5)  You should now see the new module (named “ETHERNET-MODULE 
ASD_G9ETH”) in the 1756-ENET/B branch under the I/O Configuration in 
the controller organizer view.  Right click on this new module, choose 
“Properties”, and select the Connection tab.  Refer to Figure 68. 
Confirm the setting of the Requested Packet Interval (RPI).  The RPI 
defines the amount of time (in milliseconds) between data exchanges 
across an I/O connection.  The smallest RPI supported by the interface 
card is 10ms. 
Click OK when done. 
 
 
Figure 68: Module Properties Connection Tab 
 
6)  After adding the I/O Module to the 
configuration, the full I/O 
Configuration tree should appear 
similar to Figure 69. 
 
7)  Switch to online mode and 
download the project to the PLC.  
Verify that the newly-added drive is 
available and operating correctly by 
observing any indications shown on 
the drive’s icon.  When the drive’s 
icon is selected, its status and any 
available error messages will be 
displayed in the area below the 
project tree.  Refer to Figure 70.  
Also confirm that the interface card’s 
“Network Status” LED should be 
 
Figure 69: I/O Configuration Tree 
 
Figure 70: Online Module Status