are written via the EtherNet/IP “data table write” service.  Different tags exist for 
reading vs. writing. 
 
Any given register can be accessed with its own unique tag name, or an array 
tag can be used to access a group of registers with one PLC instruction.  Tag 
names are generated according to the following structure: 
 
[action prefix][_reg_][register number] 
 
Where 
[action prefix]
 is a 2-character field, and is equal to either “rd” for read tags, or 
“wr” for write tags.  Although commonly followed for naming clarity, this “read 
vs. write” naming convention is not strictly enforced by the interface card, 
however: it is perfectly acceptable to write to a tag that starts with “rd” and read 
from a tag that starts with “wr”. 
 
[_reg_]
 is just the 5-character sequence “_reg_”. 
 
[register number]
 is a 1- to 4-character field (“1”, “2”…”1484”, “1485”) 
corresponding to the referenced register number. 
 
Examples 
Read “acceleration time 1” (register #10) ................................... rd_reg_10 
Write “option frequency command” (register #1008) .................. wr_reg_1008 
Read “inverter status 1” (register #1402).................................... rd_reg_1402 
 
Additionally, a few special tags exist which provide backward-compatibility with 
V1.000 network interface CPU firmware.  These are specified in Table 4. 
 
Table 4: Special Tag Reference 
Service 
Tag Name 
Register Start 
Same As… 
Data table read 
rd_reg_basic 
rd_reg_1 
Data table read 
rd_freq_out 
1401 
rd_reg_1401 
Data table read 
rd_inv_stat1 
1402 
rd_reg_1402 
Data table read 
rd_torq_out 
1419 
rd_reg_1419 
Data table read 
rd_inv_stat2 
1443 
rd_reg_1443 
Data table write 
wr_reg_basic 
wr_reg_1 
Data table write 
wr_cmd1 
1007 
wr_reg_1007 
Data table write 
wr_freq_cmd 
1008 
wr_reg_1008 
Data table write 
wr_cmd2 
1024 
wr_reg_1024 
Data table write 
wr_torq_cmd 
1034 
wr_reg_1034 
 
To read data from the interface card, the application PLC program must 
reference a “source element” from which to start reading and the “number of 
elements” to read.  The “source element” will be a tag name constructed 
according to the naming convention shown above, or a special tag as shown in 
Table 4.  The “source element” can be either a base tag (such as 
“rd_reg_1301”, which starts at register 1301), or an offset from a base tag (such