Toshiba ASD-G9ETH 사용자 설명서

다운로드
페이지 106
 
  
75
ICC 
as “rd_reg_1301[4]”, which starts at register 1301+4 = register 1305, the drive’s 
input voltage monitor register). 
 
In a similar manner, to write data to the interface card, the application PLC 
program must reference a “destination element” to which to start writing and the 
“number of elements” to write.  Again, the “destination element” will be a tag 
name constructed according to the naming convention shown above, or a 
special tag as shown in Table 4. 
 
Whether reading or writing, the “number of elements” can be any quantity of 
registers from 1 to the maximum allowable length (1485). 
 
 
13.2.6  ControlLogix Example: Read a Register Block 
This example program will show how to continuously read a block of registers 
from the drive with a single MSG instruction.  Only one read request is 
outstanding at any given time. 
 
1)  Create new Tags. 
a)  Double click “Controller Tags” in the controller organizer view. 
b)  The “Controller Tags” window appears.  Refer to Figure 72. 
 
 
Figure 72: Create New Tags 
 
c)  Select the “Edit Tags” tab at the bottom. 
d)  Create a new tag by entering “connection” in the first blank Name field, 
and change its Data Type to “MESSAGE”.  This tag will contain 
configuration information for the MSG instruction. 
e)  Select the “Monitor Tags” tab.  Expand the “connection” tag by clicking 
on the “+” sign next to the tag name.  Scroll down to the 
connection.UnconnectedTimeout field and change its value from the 
default 30000000 (30s in 1uS increments) to 1000000 (1s).  This value 
determines how long to wait before timing out and retransmitting a 
connection request if a connection failure occurs.  Refer to Figure 73.