c)  In this example, we will be reading a total of 25 registers beginning at 
N10:11 (register 11, the drive’s “deceleration time 1” parameter).  To 
configure this, under “This Controller” set the “Data Table Address” 
field to N18:11, set the “Size in Elements field” to 25, and set the 
“Channel” field to 1 (Ethernet). 
d)  Under “Target Device”, set the “Data Table Address” field to N10:11 
(starting target register=11) and set the “MultiHop” field to Yes to 
cause the “MultiHop” tab to appear. 
e)  Under the “MultiHop” tab settings, set the “To Address” in the first row 
to the drive’s IP address, and the “To Address” in the second row to 0.  
Refer to Figure 93. 
 
Figure 93: MSG Configuration, "MultiHop" Tab 
 
f) 
Close the dialog box.  At this point, the program should appear as 
shown in Figure 94. 
 
Figure 94: PLC Program after MSG Instruction Configuration 
 
6)  Assign a tag to the XIO element. 
a)  Double-click on the XIO element located to the left of the MSG block.  
Type in N20:0/15 (MSG instruction’s enable bit).  This configuration