Toshiba DEV002Z 사용자 설명서

다운로드
페이지 20
E6581295⑥ 
- 16 - 
Data composition of output instance 100 
Byte 
bit 
Specifications 
Supplement 
Preset speed #1*
1
 
Preset speed #2*
1
 
Preset speed #3*
1
 
Preset speed #4*
1
 
Preset speed OFF: 0000,   
Preset speed #1-#15: 0001 to 1111
A combination of 4 different bits is used 
to select a preset speed from among 
preset speed operation OFF and preset 
speed #1 to #15.   
Motor #1/#2 
(THR2 selection) 
Motor #1 
(THR1) 
Motor #2 
(THR2) 
Used to select a motor 
electronic-thermal protection level. 
0: Protection level #1 (thr) 
1: Protection level #2 (f173) 
PI control 
Normal operation
PI control off 
Acceleration/ 
Deceleration  
#1/#2 selection 
(AD2 selection) 
Acceleration/ 
Deceleration #1
(AD1) 
Acceleration/ 
Deceleration #2
(AD2) 
Used to select acceleration/deceleration 
time. 
0: acc, dec 
1: f500, f501 
DC braking 
OFF 
Forced DC 
braking 
If “1” is specified, db is displayed.   
JOG run*
2
 
OFF 
JOG run 
If “1” is specified, operation is performed 
at the frequency specified with f260
(jog run frequency).   
Forward run/ 
Reverse run 
Forward run 
Reverse run 
Run/Stop 
Stop 
Run 
Coast stop 
Ready for 
operation 
Coasting 
Emergency stop 
OFF 
Emergency stop
If “1” is specified, e tripping can occur. 
Reset 
OFF 
Reset 
Enabled only in the event of tripping   
Frequency link 
OFF 
Priority 
Enabled regardless of the setting   
of fmod 
Command link 
OFF 
Priority 
Enabled regardless of the setting   
of cmod 
 
*1: Preset speed operation can be performed at up to 15 different frequencies (preset 
speed operation frequencies #1 to #15) specified by combining preset speed 1 to 
preset speed 4. To perform preset speed operation, the “Command priority” option 
and the “Run/Stop” bit must be set to 1.   
Example: To run the motor in the reverse direction at preset speed operation 
frequency #7 (sr7)   
“10000110 00000111
” = 0x8607 (hexadecimal) 
 
If one of the bits for “Preset speed #1” to “Preset speed #4” is set to 1, priority is given 
to preset speed operation even though the “
Frequency link
” bit is set to 1, and therefore 
operation is not performed by “
Frequency link
”.   
 
*2: Jog operation has higher priority than preset speed operation. If the operation 
frequency is higher than the jog run frequency, however, jog operation is not carried 
out.