Gossen R2600 사용자 설명서

다운로드
페이지 40
GOSSEN METRAWATT GMBH
19
3.
0
Sensor error position readback
Error status 
word 2 
(heating 
current 
monitor, 
equipment)
1
Sensor error heating current
2
3
4
Heating current not "off" with positioning signal switched off
Current display
flashes
5
Heating current < 80 % of the set point of the heating current with 
active positioning signal
6
7
4.
8
EEPROM error
2)
9
10
Function error of rotary button
11
Error of measured value calibration
12
13
Invalid combination of markings
14
15
1) These error bits are deleted after reading. With LE and/or tE , the control function is reactivated.
2) EEPROM error reset by setting the standard parameters with PI = 32h.