Communications Installation - Connecting the HC900 Controller to a PC with the Hybrid Control Designer Software 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
99 
9/03  
SixNet VT-MODEM Industrial External Modem 
 
Step Action 
Connect the modem to a PC.  If your PC’s RS-232 port has a 25 pin connector, use a DB-9 
male to DB-25 female modem cable. If your PC’s RS-232 port has a 9 pin connector, use a 
DB-9 male to DB-9 female RS-232 cable.  
Connect power to the modem. You will need to supply an external power supply with a DC 
voltage between 10 and 30 VDC. 
Power-up the modem. 
Run a serial communication port program such as Hyperterminal. 
Within the communication program, select the port to which the modem is connected. 
Configure the port to these settings: 
 
baud rate = 9600, 19200, 38400, 57600 (must match baud rate configured in HC900 
   controller 
 
data bits = 8 
 
parity = none 
 
stop bits = 1 
 
flow control = none 
In the program's terminal window, restore factory defaults by keying-in the following command 
string: 
AT &F0
 
Then, press the ENTER key. 
In the program’s terminal window, key-in the following command string: 
AT E1 Q0
 
Then, press the ENTER key.  The modem should give an 
OK
 response. 
Key-in the following command string: 
AT &Y0 &C0 &D0 &R1 &S0 &K0 S0=1 
The 
Modem should respond with 
OK
10 
Key-in the following command string: 
AT E0 Q1 &W0 
The Modem will not respond. 
11 
Power down the modem and disconnect it from the PC. 
12 
Connect the modem to the RS-232 port of the HC900 Controller using a DB-9 male to DB-9 
male modem cable.  
13 
Connect the modem to a telephone jack. 
14 
Power-up the modem and the HC900 Controller. 
15 
On a remote computer, run Hybrid Control Designer software. 
16 
Set up the PC software to dial the HC900 Controller. 
17 
Use the PC software "Loop-back" feature to verify that communications are established with 
the remote HC900 Controller.