Communications Installation - RS-485 Link to Operator Interface
100
HC900 Hybrid Controller Installation and User Guide
Revision 5
9/03
RS-485 Link to Operator Interface
The RS-485 port is located below the hinged plastic cover on the top part of the Controller Module.
Typically, the cable that interconnects this port to the Operator Interface must be fabricated during
installation, because it will probably be necessary to run the cable through conduit.
Typically, the cable that interconnects this port to the Operator Interface must be fabricated during
installation, because it will probably be necessary to run the cable through conduit.
Table 18 - Parts needed for RS-485 Cabling
Part #
Quantity
Description
Belden #9271 (or equivalent),
with 120 ohm resistors (2,000
feet Maximum)
with 120 ohm resistors (2,000
feet Maximum)
Or
Belden #9182 (or equivalent),
with 150 ohm resistors (4, 000
feet maximum)
with 150 ohm resistors (4, 000
feet maximum)
Variable
Commercially available communication
cable
cable
1
10-terminal connector (Supplied with the
operator interface)
operator interface)
Phoenix #1840379 (or
equivalent)
equivalent)
1
connector (3-pin) (Supplied with the
controller CPU module)
controller CPU module)
047260 1
Ferrite cable clamps (Supplied with the
operator interface)
operator interface)
089037
2
Nylon cable ties