Communications Installation - RS-485 Link to Operator Interface 
100 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
RS-485 Link to Operator Interface 
The RS-485 port is located below the hinged plastic cover on the top part of the Controller Module.  
Typically, the cable that interconnects this port to the Operator Interface must be fabricated during 
installation, because it will probably be necessary to run the cable through conduit. 
Table 18 - Parts needed for RS-485 Cabling 
 
Part # 
Quantity 
Description 
Belden #9271 (or equivalent), 
with 120 ohm resistors (2,000 
feet Maximum) 
Or  
Belden #9182 (or equivalent), 
with 150 ohm resistors (4, 000 
feet maximum) 
Variable 
Commercially available communication 
cable 
 1 
10-terminal connector (Supplied with the 
operator interface) 
Phoenix #1840379 (or 
equivalent) 
connector (3-pin) (Supplied with the 
controller CPU module) 
047260 1 
Ferrite cable clamps (Supplied with the 
operator interface) 
089037 
Nylon cable ties