DCP552 Parameter Work Sheet
No. Item code
Item
Factory default User
Settings and descriptions
settings
settings
36
PA 36
Group 3 delay time
0.0
0.0 to 3000.0sec
37
PA 37
Group 4 event number
0
0 to 16
(0: No delay is specified.)
38
PA 38
Group 4 delay time
0.0
0.0 to 3000.0sec
39
PA 39
FAST X
0
0 : 2 X
1 : 10 X
2 : 60 X
3 : 120 X
40
PA 40
CP computation for temperature  0
-1000 to +1000 PVU (CH1)
compensation
43
PA 43
PID operation initialize (CH1)
0
0 : No initialization during advance processing and PID 
group change
1 : Initializes during advance processing but not during 
PID group change.
2 : No initialization during advance processing but initializes
during PID group change.
3 : Initializes both during advance processing and PID 
group change.
44
PA 44
PV2 message display mode
0
0 : CP or PO
2
display
1 : mV value display
2 : O
2
sensor impedance value display
45
PA 45
G.SOAK time (CH1)
2.0
0.1 to 60.0sec
46
PA 46
G.SOAK time (CH2)
2.0
0.1 to 60.0sec
51
PA 51
PV1 equalizer compensation point No. 1 Range lower
PV1 range lower limit value (tied)
limit value
52
PA 52
PV1 equalizer compensation amount No. 1 0 PVU
–1000 to +1000 PVU(PV1)
53
PA 53
PV1 equalizer compensation point No. 2 500 PVU
–19999 to +20000 PVU(PV1)
54
PA 54
PV1 equalizer compensation amount No. 2 0 PVU
–1000 to +1000 PVU(PV1)
55
PA 55
PV1 equalizer compensation point No. 3 1000 PVU
–19999 to +20000 PVU(PV1)
56
PA 56
PV1 equalizer compensation amount No. 3 0 PVU
–1000 to +1000 PVU(PV1)
57
PA 57
PV1 equalizer compensation point No. 4 1500 PVU
–19999 to +20000 PVU(PV1)
58
PA 58
PV1 equalizer compensation amount No. 4 0 PVU
–1000 to +1000 PVU(PV1)
59
PA 59
PV1 equalizer compensation point No. 5 2000 PVU
–19999 to +20000 PVU(PV1)
60
PA 60
PV1 equalizer compensation amount No. 5 0 PVU
–1000 to +1000 PVU(PV1)
61
PA 61
PV1 equalizer compensation point No. 6 2500 PVU
–19999 to +20000 PVU(PV1)
62
PA 62
PV1 equalizer compensation amount No. 6 0 PVU
–1000 to +1000 PVU(PV1)
63
PA 63
PV1 equalizer compensation point No. 7 3000 PVU
–19999 to +20000 PVU(PV1)
64
PA 64
PV1 equalizer compensation amount No. 7 0 PVU
–1000 to +1000 PVU(PV1)
65
PA 65
PV1 equalizer compensation point No. 8 3500 PVU
–19999 to +20000 PVU(PV1)
66
PA 66
PV1 equalizer compensation amount No. 8 0 PVU
–1000 to +1000 PVU(PV1)
67
PA 67
PV1 equalizer compensation point No. 9 4000 PVU
–19999 to +20000 PVU(PV1)
68
PA 68
PV1 equalizer compensation amount No. 9 0 PVU
–1000 to +1000 PVU(PV1)
69
PA 69
PV1 equalizer compensation point No. 10 Range lower
PV1 range upper limit value (tied)
limit value
70
PA 70
PV1 equalizer compensation amount No. 10 0 PVU
–1000 to +1000 PVU(PV1)
71
PA 71
PV2 equalizer compensation point No. 1 Low-limit value
PV2 range lower limit value (tied)
of range
72
PA 72
PV2 equalizer compensation amount No. 1 0 PVU
–1000 to +1000 PVU(PV2)
73
PA 73
PV2 equalizer compensation point No. 2 500 PVU
–19999 to +20000 PVU(PV2)
74
PA 74
PV2 equalizer compensation amount No. 2 0 PVU
–1000 to +1000 PVU(PV2)
75
PA 75
PV2 equalizer compensation point No. 3 1000 PVU
–19999 to +20000 PVU(PV2)
76
PA 76
PV2 equalizer compensation amount No. 3 0 PVU
–1000 to +1000 PVU(PV2)
77
PA 77
PV2 equalizer compensation point No. 4 1500 PVU
–19999 to +20000 PVU(PV2)
78
PA 78
PV2 equalizer compensation amount No. 4 0 PVU
–1000 to +1000 PVU(PV2)
denotes items settable only on models with CP compensation