Honeywell DCP552 Mark II 사용자 설명서

다운로드
페이지 247
3
DCP552 Parameter Work Sheet
No. Item code
Item
Factory default User
Settings and descriptions
settings
settings
79
PA 79
PV2 equalizer compensation point No. 5 2000 PVU
–19999 to +20000 PVU(PV2)
80
PA 80
PV2 equalizer compensation amount No. 5 0 PVU
–1000 to +1000 PVU(PV2)
81
PA 81
PV2 equalizer compensation point No. 6 2500 PVU
–19999 to +20000 PVU(PV2)
82
PA 82
PV2 equalizer compensation amount No. 6 0 PVU
–1000 to +1000 PVU(PV2)
83
PA 83
PV2 equalizer compensation point No. 7 3000 PVU
–19999 to +20000 PVU(PV2)
84
PA 84
PV2 equalizer compensation amount No. 7 0 PVU
–1000 to +1000 PVU(PV2)
85
PA 85
PV2 equalizer compensation point No. 8 3500 PVU
–19999 to +20000 PVU(PV2)
86
PA 86
PV2 equalizer compensation amount No. 8 0 PVU
–1000 to +1000 PVU(PV2)
87
PA 87
PV2 equalizer compensation point No. 9 4000 PVU
–19999 to +20000 PVU(PV2)
88
PA 88
PV2 equalizer compensation amount No. 9 0 PVU
–1000 to +1000 PVU ( PV2 )
89
PA 89
PV2 equalizer compensation point No. 10 Range upper 
PV2 range upper limit value (tied)
limit value
90
PA 90
PV2 equalizer compensation amount No. 10 0 PVU
–1000 to +1000 PVU(PV2)
93
PA 93
Auto-tuning (CH2)
0
0 : AT not performed
1 : standard AT performed on currently used PID group in 
mode other than READY mode.
2 : AT writing overshoot-proof PID values to currently used 
PID groups in mode other than READY mode performed.
3 : Standard AT performed on PID groups A1 to A7 in 
READY mode.
4 : AT writing overshoot-proof PID values to PID groups A1 
to A7 in READY mode continuously performed.
94
PA 94
Auto-tuning MV lower limit (CH2) 0.0
-5.0 to upper limit %
95
PA 95
Auto-tuning MV upper limit (CH2) 100.0
Lower limit to +105%
96
PA 96
PID computation initialize (CH2) 0
0 : No initialization during advance processing and PID 
group change
1 : Initializes during advance processing but not during PID 
group change
2 : No initialization during advance processing but 
initializes during PID group change
3 : Initializes both during advance processing and PID 
group change
97
PA 97
CPU computation compensation 0
0 : no compensation
1 : compensates
98
PA 98
CP value (PV) display lower limit value 0.000
0 to upper limit SPU (CH2)
99
PA 99
CP value (PV) display upper limit value 4.000
lower limit to 4000 SPU (CH2)
100
PA100
Gas constant
23.5
10.0 to 50.0
101
PA101
CP computation compensation 0.000
0 SPU (CH2) (tied)
No.1 compensation point
102
PA102
CP computation compensation 0.000
-1000 to +1000 SPU (CH2)
No.1 compensation amount
103
PA103
CP computation compensation 0.200
0 to 2000 SPU (CH2)
No.2 compensation point
104
PA104
CP computation compensation 0.000
-1000 to +1000 SPU (CH2)
No.2 compensation amount
105
PA105
CP computation compensation 0.400
0 to 2000 SPU (CH2)
No.3 compensation point
106
PA106
CP computation compensation 0.000
-1000 to +1000 SPU (CH2)
No.3 compensation amount
107
PA107
CP computation compensation 0.600
0 to 2000 SPU (CH2)
No.4 compensation point
108
PA108
CP computation compensation 0.000
-1000 to +1000 SPU (CH2)
No.4 compensation amount
109
PA109
CP computation compensation 0.800
0 to 2000 SPU (CH2)
No.5 compensation point
110
PA110
CP computation compensation 0.000
-1000 to +1000 SPU (CH2)
No.5 compensation amount
denotes items settable only on models with CP compensation