Installing and Cabling the Cabinets
48 Installation, Upgrades and Additions for Avaya CMC1 Media Gateways
 
Install Coupled Bonding Conductor 
The Coupled Bonding Conductor (CBC) provides for mutual inductance coupling between the 
CBC and the telephone cables that are exposed to lightning. The conductor can be a 10 AWG 
(#25) (6 mm
2
) wire tie wrapped to the exposed cables, a metal cable shield around the exposed 
cables, or 6 spare pairs from the exposed cable. 
In a high rise building, connect the CBC to an approved building ground on each floor. To 
provide the coupled bonding protection:
1. Connect 1 end of the conductor to a telephone cable building entrance protector ground that 
is connected to an approved ground.
2. Route the rest of the conductor next to the exposed telephone cables being protected until 
they reach the cross-connect nearest to the telephone system.
3. Position the non-exposed telephone cables at least 12 inches (30.5 cm) away from exposed 
telephone cables whenever possible.
4. Terminate the other end to the single-point ground block provided for the telephone system.
Connect and Route Cabinet AC Power Cords
!
CAUTION:
CAUTION:
The AC power cords may connect to a properly rated power distribution unit, 
individual AC power receptacles, or to a UPS. See 
To connect and route cabinet AC power cords:
1. Be sure the circuit breakers at the AC load center are OFF
2. Connect Cabinet A to an “unswitched” or “always on” electrical outlet.