Avaya CMC1 사용자 설명서

다운로드
페이지 370
Installing and Cabling the Cabinets
46 Installation, Upgrades and Additions for Avaya CMC1 Media Gateways
 
Connect Cabinet Grounds and Other Grounds
The following additional grounding requirements must be met:
The approved ground wire must be green, 6 AWG (#40) (16 mm
2
), copper, stranded wire 
(this is in addition to the ground wire in the AC power cord)
Bond all approved grounds at the single-point ground to form a single grounding electrode 
system
Install the Ground Block
To install the ground block
1. Mount the ground block as shown in 
2. Make the cable connections as shown in 
.
Figure 10: Ground Block Installation to Right Panel
Figure notes:
1. #12 x 1-inch shoulder screws
2. Single-point ground block
indmingb RPY 012398
1
2
2
A