Programming and Set-Up - Programming the UPS
990-2440
AIS 5000 400V Installation Manual
67
Battery Monitor Reset
This parameter will only appear on the 
display if the Advanced Battery Monitor 
option is installed.
To reset the battery monitor, push 
 and 
browse through the menu, using the 
cursor keys
 
 or 
 until the
display shows:
To reset the Battery Monitor Alarms, press
.
Settings for redundant systems
Adaptive Slew Rate
To program the UPS for Adaptive Slew Rate, 
press 
.
Browse through the menu, using the 
cursor keys
 
 or 
 until the
display shows:
Select Adaptive Slew Rate by pressing
.
Deactivate by pressing 
.
Enter New Date
To program the date setting, press 
.
Browse through the menu, using the 
cursor keys
 
 or 
 until the
display shows:
Enter the new date by using the numeric keys. 
Enter the year, month, and day.
Store the by pressing 
.
Battery Monitor
Reset: OFF
Adaptive
Slew Rate: OFF
Enter new date
YY.MM.DD