69
Setting stack
In the setting stack, the following parameters are changeable:
Parameter
Factory Setting
Normal Charge Voltage
272 Vdc
Boost Charge Voltage
272 Vdc - no boost required
Charge Current Max.
Refer to below table
Low Battery Warning
216 Vdc
Low Battery Shutdown
204 Vdc
Boost Charge Time
8 hours
Slew rate 0 – 4
1 Hz
Charger ON/OFF
ON
Inverter and Bypass ON/OFF
ON
Battery Back-up Time
Until a battery capacity test has been 
performed, display will show xxx
High Battery Temperature
35
o
C
Auto Battery Monitor
ON
Battery Summary Error
OFF
Remote Shutdown
OFF
Remote Shutdown Polarity
HIGH
Remote Shutdown Time
2 minutes
Max. Charge Current
UPS
A
DC
10 kVA
5
20 kVA
10
30 kVA
15
40 kVA
20
60 kVA
30
80 kVA
40
100 kVA
50