Programming and Set-Up - Operation Modes
72
AIS 5000 400V Installation Manual
990-2440
Normal to Bypass Operation
If the bypass mains fails during bypass operation, the UPS will automatically switch to normal 
operation, provided that the rectifier mains is available. If the battery supply is available, and within 
the tolerance range, the UPS will switch to battery operation.
Bypass to Normal Operation
Press 
 
and the cursor keys 
 or 
 until the display shows:
Press 
. If the bypass mains is within the tolerance range, the UPS will 
transfer to electronic bypass. The display shows: 
Note
The load is now supplied directly from the bypass mains.
Note
Depending on the programming, a short loss of output voltage may occur.
Bypass Operation:
OFF
Bypass Operation
1. Press 
 and the cursor keys 
 or 
 until the display shows:
2. Press 
 The display will show:
Note
The load is now supplied by the UPS.
Bypass Operation:
ON
Normal Operation
Load Power xx%