Operation Modes
The display automatically indicates the current UPS operation mode. See the table below for
examples of operation modes and their descriptions.
examples of operation modes and their descriptions.
Operation mode descriptions:
Operation Mode
Description of Operation Mode
Normal Operation
The inverter supplies the load. The charger uses the mains supply to feed the
inverter.
inverter.
Battery Operation
The inverter supplies the load. The battery bank supplies the inverter. In battery
operation the load support time is limited; when the batteries are discharged the
UPS is unable to supply the load.
operation the load support time is limited; when the batteries are discharged the
UPS is unable to supply the load.
Bypass Operation
The bypass static switch supplies the load, meaning that the load is supplied
directly from the bypass mains. When working in bypass operation the UPS can
switch to battery operation if the bypass mains fails.
directly from the bypass mains. When working in bypass operation the UPS can
switch to battery operation if the bypass mains fails.
Charger Only
The charger is recharging the battery. The inverter is shut down.
Economy Operation
The UPS is in permanent bypass operation and will only switch to battery
operation if the bypass mains is out of tolerance.
operation if the bypass mains is out of tolerance.
Hot Standby
In redundant configurations, one UPS can switch off the inverter, but still keep
the inverter ready for immediate start in case another UPS fails.
the inverter ready for immediate start in case another UPS fails.
Note
In standby mode, the UPS has no output voltage.
Note
Users do not require electrical qualifications to switch the UPS to and from standby
mode/normal operation.
mode/normal operation.