Emerson BACNET IP 사용자 설명서
Modbus 485 and Modbus IP Protocols - UPS Systems
205
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 73
Liebert Npower
™
- Input and Holding - IMP
Controller
Single Module Series - SMS
Liebert Products
Liebert Npower - SMS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Status Points (View)
Input Voltage A-B
Input Voltage A-B
—
40001
1
—
V
Input Voltage B-C
—
40002
1
—
V
Input Voltage C-A
—
40003
1
—
V
Bypass Voltage A-B
—
40004
1
—
V
Bypass Voltage B-C
—
40005
1
—
V
Bypass Voltage C-A
—
40006
1
—
V
Battery Voltage
—
40007
1
—
V
Battery Current
—
40008
1
10
A
Battery Temperature
—
40009
1
—
deg C
Output Voltage A-B
—
40010
1
—
V
Output Voltage B-C
—
40011
1
—
V
Output Voltage C-A
—
40012
1
—
V
Output Current A
—
40013
1
10
A
Output Current B
—
40014
1
10
A
Output Current C
—
40015
1
10
A
Output kVA A
—
40016
1
—
kVA
Output kVA B
—
40017
1
—
kVA
Output kVA C
—
40018
1
—
kVA
Output kW A
—
40019
1
—
kW
Output kW B
—
40020
1
—
kW
Output kW C
—
40021
1
—
kW
Output Frequency
—
40022
1
10
Hz
Rated kVA Percentage
—
40023
1
—
%
Rated kW Percentage
—
40024
1
—
%
Alarm Points
Communications Loss
Communications Loss
—
40289
1
—
Bit 0
Battery Fuse Fail
—
40289
1
—
Bit 1
Battery Low Transfer
—
40289
1
—
Bit 2
DC Over Voltage Transient
—
40289
1
—
Bit 3
Input Phase Rotation Error
—
40289
1
—
Bit 4
Rectifier/Trap Fuse Fail
—
40289
1
—
Bit 5
Any of Rectifier / Trap Fuse
Bypass Frequency Error
—
40289
1
—
Bit 6
Bypass Overload Shutdown
—
40289
1
—
Bit 7
Bypass Phase Rotation Error
—
40289
1
—
Bit 8
Inverter Over Voltage Transfer
—
40289
1
—
Bit 9
Inverter Fuse Fail
—
40289
1
—
Bit 10
Output Over Voltage Transfer
—
40289
1
—
Bit 11
Output Under Voltage Transfer
—
40289
1
—
Bit 12
SBS SCR Open
—
40289
1
—
Bit 13
SBS SCR Short
—
40289
1
—
Bit 14
Inverter Over Current Transfer
—
40289
1
—
Bit 15