3. Setup
1) Secure the legs to the remote condenser 
unit with the 8 bolts and nuts provided. 
See Fig. 5.
) The legs have 8 mounting holes. Secure 
the legs with 8 bolts (not included).
 Fig. 5
4. Line Set
CAUTION
The icemaker, line set, and remote condenser unit must contain the same 
type of refrigerant. Mixing of refrigerants will result in improper operation and 
possible damage to the refrigeration system.
• Precharged factory line sets, available as optional equipment from Hoshizaki America, are 
recommended. For details, see "II.F.4.a) Factory Line Set Installation." Field fabricated 
line sets are allowed. For details, see "II.F.4.b) Field Fabricated Line Set Installation."
• The maximum line length for the standard refrigerant charge is 66 feet. Should an 
installation require a longer line length, line sizes must be increased and additional 
refrigerant must be added. Instead of the standard 3/8" OD discharge line and 1/4" OD 
liquid line for this icemaker, increase the line sizes to 1/" OD discharge line and 3/8" OD 
liquid line for the entire run. Add 16.5 oz. of R-404A to the system to compensate for 
the larger diameter line sizes, then add .4 oz. of R-404A for each foot over 66 feet to a 
maximum of 100 feet. Hoshizaki Technical Support is available at 1-800-33-1940 for 
recommendations.
• The maximum vertical distance between the remote condenser unit and the icemaker 
is 33 feet above or 10 feet below the icemaker. These distances are measured fitting to 
fitting.
a) Factory Line Set Installation
1) Route the factory line set (3/8" OD discharge line and 1/4" OD liquid line) from the 
remote condenser unit to the icemaker. Leave a service loop behind the icemaker to 
allow the icemaker to be pulled out for service. See Fig. 6. Factory fabricated line sets 
are precharged and do not need to be evacuated.
CAUTION
1. Ensure that there are no traps and no kinks in the line set.
. Do not coil extra line set. If the line set is too long, recover the line set 
charge and store it in an approved container. Do not discharge the 
refrigerant into the atmosphere. Remove the extra line set length, braze 
the connections, then skip to step 4 in "II.F.4.b) Field Fabricated Line Set 
Installation." 
Bolts with Split 
Lock Washer 
and Flat Washer
Nuts