Hoshizaki FD-1001MAH(-C) 사용자 설명서

다운로드
페이지 44
3
G. Connection to an R-404A Parallel Rack System
 WARNING
1. Installation must be performed by properly trained and EPA-certified service 
personnel.
. Failure to install the equipment within these guidelines may adversely affect 
safety, performance, component life, and warranty coverage.
3. The icemaker, line set, and rack system must contain the same type of 
refrigerant. Mixing of refrigerants will result in improper operation and 
possible damage to the refrigeration system.
• The rack system must be sized to provide a maximum load of 5,700 BTU/h at 90°F (3°C) 
ambient temperature and 70°F (1°C) water temperature.
• Install a p-trap in the suction line if required by the rack system's instructions. 
• The evaporator pressure regulator (EPR) valve is factory adjusted to sustain a suction 
pressure of 31 PSIG for a -°F (-19°C) evaporator temperature. Adjust only if necessary.
• The icemaker is shipped with a holding charge of 3.5 oz. of R-404A.
• Charging port-equipped Parker quick connect couplings are needed to connect the line 
set to the icemaker. 
1. Line Set Installation
1) Route a 3/8" OD copper tube suction line and a 1/4" OD copper tube liquid line between 
the icemaker and the rack system. Leave a service loop behind the icemaker to allow 
the icemaker to be pulled out for service. See Fig. 11. 
CAUTION
Do not coil extra line set. Fabricate the line set to the proper length.
) Insulate the  copper tubes separately. 
3) Braze the charging port-equipped Parker quick connect couplings to the icemaker end 
of the copper tubes. Do not connect the charging port-equipped Parker quick connect 
couplings to the icemaker at this time.
4) When using couplings to connect the line set to the rack system, braze them to the 
rack system end of the copper tubes. Otherwise, braze the line set directly to the rack 
system. Do not open the rack system service valves at this time.
5) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of 
refrigerant to the line set copper tubes (if using an electronic leak detector), and then 
raise the pressure using nitrogen gas (140 PSIG). 
WARNING! DO NOT use R-404A 
as a mixture with pressurized air for leak testing. 
6) Evacuate the line set copper tubes through the charging ports on the Parker quick 
connect couplings and charge with R-404A refrigerant vapor to a pressure of 15 to 
30 PSIG.