Diagnostics over Industrial Ethernet 
 
6.2 Web Based Management (WBM) 
6.2.4.3 
The "System Restart & Defaults" WBM Menu 
System Restart & Defaults 
In this screen, there is a button with which you can restart the device and various options for 
resetting to the device defaults. 
 
Figure 6-8 
"System Restart & Defaults" Dialog 
Restart System Button 
Click this button to restart the SCALANCE X-200. You must confirm the restart in a dialog 
box. During a restart, the SCALANCE X-200 is reinitialized, the internal firmware is reloaded, 
and the SCALANCE X-200 runs a self-test. The learned entries in the address table are 
deleted. You can leave the browser window open while the SCALANCE X-200 restarts. 
Restore Memory Defaults Button 
Click on this button to restore the factory configuration settings with the exception of the 
following parameters: 
•  IP address 
•  Subnet mask 
•  Gateway address 
•  IP address of the default router 
•  DHCP flag 
•  System name 
•  System location 
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line 
Commissioning Manual, 1,   