Configuration / diagnostics using remote mechanisms 
 
6.3 Configuration using Web Based Management (WBM) and Command Line Interface (CLI) 
SCALANCE X-200 
Operating Instructions, 12/2011, A5E00349864-19 
229
 
●  "Source Port" display box 
Shows the port that received the frame that triggered the last reaction. 
●  "Action" button 
After the loop in the network has been eliminated, you can use this button to reset the 
port again. 
NOTICE 
 
 
A loop is an error in the network structure that needs to be eliminated. The loop 
detection can help to find the errors more quickly but does not eliminate them. The loop 
detection is not suitable for increasing network availability by deliberately including 
loops. 
NOTICE 
 
 
Loops can only be detected between devices that forward loop detection frames. Loops 
via network components whose ports are set to "blocked" are not detected. 
 
 
Note 
Test frames create additional network load. We recommend that you only configure 
individual switches, for example at branch points of the ring, as "senders" and the others 
as "forwarders". 
 
Syntax of the Command Line Interface 
Table 6- 31  Loop Detection Configuration - CLI\SWITCH\LOOPD > 
Command 
Description 
Comment 
info 
Displays information about the "Loop Detection 
Configuration". 
 
loopd [E | D] 
Enables / disables loop detection. 
Administrator only. 
loopdp <port> 
[B | F | S] 
Defines the behavior of a port for loop detection: 
 
"Blocked" 
 
"Forwarder" 
 
"Sender" 
Administrator only. 
rxthres <port> 
<count>  
Specifies the Rx.Threshold. 
Administrator only. 
local <port> [N | 
D] 
Specifies the reaction to a local loop. 
Administrator only. 
remote <port> 
[N | D] 
Specifies the reaction to a remote loop. 
Administrator only. 
reset <port>  
Reactivates the port if it was deactivated due to a detected 
loop. 
Administrator only.