Emerson XDF 사용자 설명서

다운로드
페이지 60
Operation
47
10.8 Backup Ventilation System
The XDF is equipped with a backup ventilation system that circulates ambient air through the XDF 
should any component of the cooling system fail or if power is lost. The backup ventilation system 
begins operating only after the internal temperature exceeds the ambient external temperature.
If powered by a UPS, evaporator fans circulate ambient air until the XDF returns to normal opera-
tion.
Figure 35 Airflow pattern, backup ventilation operation
10.9 XDF Compressor
The iCOM automatically adjusts the cooling capacity of the digital scroll compressor depending on the 
heat load in the cabinet.
Sensors near the evaporator fans monitor the cooling airflow and send the data to the iCOM. These 
sensors have setpoints that may be adjusted with the iCOM control unit to raise or lower the internal 
cabinet temperature. For information on changing the setpoints, refer to 10.6 - Changing the XDF’s 
Default Operating Temperature or call 800-543-2778.
If the return air temperature drops below the setpoint, iCOM reduces the compressor’s cooling output 
accordingly. The evaporator fans will continue to circulate internal cabinet air throughout the enclo-
sure.
10.10 Uninterruptible Power Supply 
The XDF may be supplied with any of several Liebert UPS units or with no UPS. For inte-
grated/matched models, the UPS and the equipment installed in the XDF are sized with matched 
capacities. A larger UPS, with more battery time, can be obtained, but the connected electronics load 
should not exceed the XDF’s cooling capacity.
For XDF units equipped with a UPS, refer to the UPS manual for UPS operation and specifications.
Backup Ventilation Air 
Exhaust Vent
Heated air returns
Evaporator Fans
circulate cooling air 
if powered by a UPS
Backup Ventilation Air 
Intake Vent
Self-contained, air cooled 
XDF shown; vents and
operation apply to all XDF 
models