Maintenance
48
11.0 M
AINTENANCE
11.1 Periodic Maintenance
The Liebert XDF requires very little maintenance. The XDF’s condenser coil must be inspected peri-
odically to determine the necessary cleaning interval based on conditions at the installation site. 
Depending on site conditions, the coil may require cleaning as often as twice a month or as seldom as 
twice per year. If the coil becomes dirty and clogged, it should be vacuumed with a soft bristle brush 
or cleaned with compressed air.
Table 9
Troubleshooting
Problem
Cause
Solution
XDF system not cooling
No Power
Confirm unit is plugged in and the building breaker has not 
tripped.
Clogged condenser coil
Hot Gas bypass valve set 
incorrectly
Contact Liebert Technical Support at 800-543-2378.
Refrigerant loss
Verify leak. If refrigerant system needs repaired, contact 
Liebert Technical Support at 800-543-2378.
Fans blowing warm air
Airflow is blocked at the intake 
or exhaust.
Remove airflow obstructions from the front and rear of the 
enclosure. Ensure the cabinet has at least 36" (915mm) 
front, rear and overhead clearance. (Water/glycol models 
do not require overhead clearance.) Open XDF’s doors and 
let compressor cool. Plug in XDF and verify compressor is 
energized.
Compressor trips on thermal 
overload
Open XDF doors and let compressor cool. Plug in XDF and 
verify compressor is energized.
Faulty Compressor
Contact Liebert Technical Support at 800-543-2378.
Water leaking from inside 
the cabinet
Cabinet not level or internal 
drain line clogged
Ensure that the enclosure rests on a level surface. The 
cabinet must be level to ensure proper operation. Verify 
condensate drain is attached to drain and the drain line has 
the proper pitch (see 4.5.4 - Condensate Drain 
Excessive vibration or 
noise
Defective motor in blower or 
shipping damage
 Contact Liebert Technical Support at 800-543-2378.
Cabinet is excessively hot
Electronic equipment not 
positioned for optimum cabinet 
airflow
Rearrange the equipment as illustrated in 4.7 - Equipment 
Compressor is overloaded
Verify the UPS load does not exceed XDF’s capacity. If no 
UPS, verify equipment load does not exceed the XDF’s 
rating.
Heat not rejected from room
Verify that XDF is in room with air circulation and heat 
rejected from unit is sufficiently removed.
XDF system not cooling
Confirm unit is plugged in and the building breaker has not 
tripped. Check setpoints on iCOM controller.
Cabinet not sealed
Check cable entry points, and verify doors and side panels 
are closed. Reposition wires to prevent air leak, or fix or 
replace damaged gaskets.
Audible alarm and cabinet 
is excessively hot
iCOM control module has 
detected an abnormal condition
Silence alarm on the iCOM module. See solutions for “XDF 
is excessively hot causes” to determine course of action.