Emerson XDF 사용자 설명서
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
Specifications
50
Table 11
Electrical specifications
Electrical Data
Self- Contained,
Air Cooled XDF
Water/Glycol
Cooled XDF
Control & Fan Supply
Voltage
120
120
Ph
1
1
Hz
60
60
Unit FLA
8.3
5.0
Max Fuse or Circuit Breaker Amps
15
15
Min. Supply Circuit Ampacity
9.2
5.2
Receptacle required
NEMA 5-15R
NEMA 5-15R
Compressor Supply
Voltage
208
208
Ph
3
3
Hz
60
60
Unit FLA
15.7
15.7
Max Fuse or Circuit Breaker Amps
35
35
Min. Supply Circuit Ampacity
19.6
19.6
Receptacle required
NEMA L21-30R
NEMA L21-30R
Condensate Pump Amps (Optional)
0.72
0.72
Table 12
Total heat rejection
Rating Point,
Ambient
°F (°C)
Supply Air
Temperature,
°F (°C)
Load, kW
Total Heat
Rejection, kW
95 (35)
77 (25)
14.1
20