Emerson XDF 사용자 설명서

다운로드
페이지 60
Specifications
50
Table 11
Electrical specifications
Electrical Data
Self- Contained,
Air Cooled XDF
Water/Glycol 
Cooled XDF
Control & Fan Supply
 Voltage
120
120
 Ph
1
1
 Hz
60
60
 Unit FLA
8.3
5.0
 Max Fuse or Circuit Breaker Amps
15
15
 Min. Supply Circuit Ampacity
9.2
5.2
 Receptacle required
NEMA 5-15R
NEMA 5-15R
Compressor Supply
 Voltage
208
208
 Ph
3
3
 Hz
60
60
 Unit FLA
15.7
15.7
 Max Fuse or Circuit Breaker Amps
35
35
 Min. Supply Circuit Ampacity
19.6
19.6
 Receptacle required
NEMA L21-30R
NEMA L21-30R
 Condensate Pump Amps (Optional)
0.72
0.72
Table 12
Total heat rejection
Rating Point,
Ambient
°F (°C)
Supply Air
Temperature,
°F (°C)
Load, kW
Total Heat
Rejection, kW
95 (35)
77 (25)
14.1
20