Installing the System 
22
Connecting the Hospitality Adjuncts 
Switch-to-INTUITY Admin Link (X.25)
This data link transfers information to support the INTUITY AUDIX service for 
office staff voice messaging. This connection will be used only if:
Your system has been upgraded from an earlier system, and
The customer chooses to retain their X.25 hardware (a PI circuit pack is 
needed on the 
si system, or a Packet Gateway circuit pack is needed on an 
r system) instead of the TCP/IP C-LAN hardware. 
Se
. For installations using 
Mode Code integration, see 
NOTE:
The connectivity shown in this section will not work on an 
si system with 
duplication. For a duplicated system, the connection between the switch 
and the INTUITY is done with DCP data modules. See your project 
manager for more information.
Parts List
A PI port (TN765) on an 
si system, or a Packet Gateway port (TN577) on 
an 
r system
One H600-347 cable (
r system only)
One H600-210 Group 3 cable (50 feet; 15.2 meters)
One 105C IDI (comcode 107422735) or 105D IDI (comcode 108367376)
An IDI provides electrical isolation and protection between the switch and 
the INTUITY hardware. The dip switch settings on the IDI must be set for 
“Direct Connect.”
One ED1E434-11 Group 175 cable (4.5 feet; 1.5 meters)
One DCIU card (comcode 406801647, J1P260AA, L31) installed in the 
MAP, usually located in slot 1.