Functions 
 
3.7 System monitoring 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
37
 
Connector monitoring 
Line-side connector monitoring can be deactivated via the DIP switch. 
For more information, see Parameterization via local setting (Page 72). 
Response when connector is unplugged  
When the connector is unplugged, the motor starter outputs a group fault. 
Settings  
 
Device parameter 
Default setting 
Setting range 
Connector monitoring 
Line side 
• 
Deactivated 
• 
Line side 
3.7.5.2 
Motor connector 
The "connector monitoring" function is only valid for the infeed connector.  
A connector monitoring function for the motor connector can be logically combined with the 
thermistor cable and/or thermistor evaluation function.  
If a motor is operated without a thermistor, you can activate thermistor monitoring 
(thermoclick) and use it to monitor the connector by means of a wire jumper on the motor 
terminal board or in the motor connector.   
 
 
Note 
The "overload" message must be interpreted to mean that the motor connector has been 
unplugged.