CDV Series Direct Vent Gas Fireplace
20010175
The vent chart should be read in conjunction with the 
following vent installation instructions to determine the 
relationship of the vertical and horizontal dimensions of 
the vent system.
1.  Determine the height of the center of the horizontal 
vent pipe exiting through the outer wall.  Using this 
dimension on the Sidewall Vent Graph (Fig. 11) 
locate the point intersecting with slanted graph line. 
2.  From the point of this intersection, draw a vertical 
line to the bottom of the graph.
3.  Select the indicated dimension, and position the 
fireplace in accordance with same. 
  Example A:
  If the vertical dimension from the floor of the    
fireplace is 11’ (3.4 m) the horizontal run to the face  
of the outer wall must not exceed 14’ (4.3 m).
  Example B:
  If the vertical dimension from the floor of the unit is  
7’ (2.14 m), the horizontal run to the face of the outer  
wall must not exceed 8¹⁄₂’ (2.6 m).
How to Use the Vent Graph
Horizontal dimension from the outside face of the 
wall to the center of the fireplace vent flange
Sidewall vent graph showing the relationship between vertical        
and horizontal dimensions for a Direct Vent flue system.
V
ertical dimension from the fl
oor of the unit
to the center of the horizontal vent pipe
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
3     4    5    6    7   8    9  10  11 12  13 14  15 16  17 18  19  20
eg:  A
eg:  B
CFM102 
DV Graphic
9/28/00   sta
Fig. 11  Sidewall venting graph. (Dimensions in feet)
Rear Wall Venting Applications
* Exterior Outside Wall 
7” (178 mm) to 13” (330 mm) 
From Rear of Unit *
When installed as a rear vent unit this appliance may 
be vented directly to a termination located on the rear 
wall behind the appliance. 
• 
Only CFM Corporation venting components are 
approved to be used in these applications. (Refer to 
“Venting Components” listed for different installation 
requirements)
• 
The maximum straight horizontal distance be-
tween the rear of the appliance and the outside 
face of the rear wall is 13” (330 mm). The mini-
mum is 7” (178 mm). (Fig. 12)
 
• 
Minimum clearances between vent pipe and com-
bustible materials are as follows:
 
Top - 1” (25 mm)
 
Sides - 1” (25 mm)
 
Bottom - 1” (25 mm)
Twist Lock Pipes
When using CFM Corporation twist-lock pipe, it is not 
necessary to use sealant on the joints. The only areas 
of the venting system that need to be sealed with high 
temperature silicone sealant are the sliding joint of any 
telescopic vent section used in the system.
To join the twist lock pipes together, simply align the 
beads of the male end with the grooves of the female 
end, then while bringing the pipe together, twist the pipe 
until the flange on the female end contacts the external 
flange on the male end. It is recommended that you 
secure the joints with three (3) sheet metal screws, 
however this is not mandatory with twist lock pipe.
To make it easier to assemble the joints we suggest 
putting a lubricant (Vaseline or similar) on the male end 
of the twist lock pipe prior to assembly. 
36CDVR Venting
TWL100
Twist Lock Pipe
3/12/99   djt
Male End
Female End
Screw Holes
TWL100
Fig. 10  Twist-lock pipe joints.