CDV Series Direct Vent Gas Fireplace
20010175
Top View
Straight Venting
Fig. 12  Rear vent applications.
13" 
(330 mm)
Max.
������
���������
���������
�����
FP1598
Rear Wall Installation
Twist Lock Pipe
STEP 1
Locate vent opening on the wall. To locate hole center 
consult with appropriate fireplace dimensions, Page 4. 
Frame as shown below.
Combustible Walls (Fig. 13)Cut a 9³⁄₈”H x 9³⁄₈” W 
(240 x 240 mm) hole through the exterior wall and 
frame as shown. 
Noncombustible Walls (Fig. 13): Hole opening must 
be 7¹⁄₂” (190 mm) in diameter. 
VO584-100
Vent Opening
2/99   djt
Vent Opening for Combustible Wall
9³⁄₈”
(240 mm)
9³⁄₈”
(240 mm)
Fireplace Hearth
Framing 
Detail
Opening for Noncombustible Wall
7¹⁄₂”
(190 mm)
VO584-100
Fig. 13  Locate vent opening on wall.
STEP 2
Install interior firestop as shown in Figure 14.
STEP 3
Remove telescoping collar from termination.
STEP 4
Bend tab on outer casing up and insert collar onto fire-
place collars. (Fig. 14)
������
��������
������
Firestop
FP1600
Fig. 14  Install firestop.
Bend Tab
FP1005
Side View Vent Termination
1/25/00   djt
22”
(559 mm)
CL
Finished 
Wall
Secure with Screw
Vent Termination
Firestop
FP1005a
Fig. 15  Side view of final unit location.
STEP 5
Twist the termination collar so it locks onto fireplace col-
lars. Run screw through tab to keep collar from turning. 
(Fig. 15)
STEP 6
Slide fireplace into position.
STEP 7
From the outside of the house, slide the termination 
onto the collars.
STEP 8
Secure the termination to the house with the four (4) 
screws provided.