Vermont Casting DVT38IN 사용자 설명서

다운로드
페이지 48
19
Chateau™
20011956
Sidewall Applications
��
��
��
��
��
��
��
��
��
��




���
���


� �
� �� �� �� �� �� �� �� �� �� �� ��
Vertical Run (in feet)
(Measured from the appliance flue collar to the top of the vent
 pi
pe.)
Horizontal Run (in feet)
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
FP1359
DVT44
Horizontal
venting 
graph
5/13/03  djt
May use up to 
three (3) 90° 
elbows, but must 
not have two (2) 
consecutive 90° 
elbows in horizon-
tal plane
Unacceptable vent-
ing configuration
FP1359
Fig. 16  Horizontal vent termination window.
May use 
one (1) 
elbow 
only
Since it is very important that the vent-
ing system maintain its balance between 
the combustion air intake and the flue 
gas exhaust, certain limitations as to vent 
configurations apply and must be strictly 
adhered to.
NOTE: The penetration to the outside of the build-
ing or structure shall be sealed air and weather 
tight.
Use of the Restrictor Plates in
Horizontal Venting Applications
The primary purpose for the vent restrictor plate is to 
regain flame height under certain venting conditions as 
outlined below.
The DVT38IN is shipped with the fresh air plate set-
tings at #4 (this applies to both natural gas and 
propane) when using the horizontal starter vent kit 
SK8DVSK.
Minimum clearance between vent pipes 
and combustible materials is 3¹⁄₂” (89 mm) 
on top, 2¹⁄₂” (64 mm) on both sides and 1¹⁄₂” 
(38 mm) on the bottom.
When the vent termination exits through foundations 
less than 20” (508 mm) below siding outcrop, the vent 
pipe must be flush with the siding.
It is always best to locate the fireplace in such a way 
that minimizes the number of offsets and horizontal 
vent length of vent pipe from the flue collar of the fire-
place to the face of the outer wall. 
Horizontal plane means no vertical rise exists on this 
portion of the vent assembly. 
NOTE:  Apply high temperature sealant or UL approved 
high temperature metal adhesive tape as directed on Page 
12.
FP1012
Top vent max run
1/25/00   djt
14’
 (4.3m)
Pipe Straps 
Every 3’ (914 
mm)
Firestop/Zero 
Clearance Sleeve
Pipe 
Straps 
Every 3’ 
(914 mm)
20’ (6 m)
FP1012a
Fig. 17  Support straps for horizontal runs.
Minimum 2’ (610 
mm) Section
Unitized Elbow 
(SK890)
• 
The maximum number of 90° elbows per side wall 
installation is three (3), but must not have two (2) 
consecutive elbows in the horizontal plane.
• 
A minimum of 2’ (610 mm) vertical section off the top 
of the unit is required, an elbow and a 1’ (305 mm) 
maximum horizontal run to get through a wall. (Fig. 
18)
2'
(610mm)
FP1237a
DVT44
horizontal plane
4/03
2'
(610mm)
CL
X
FP1237a
Fig. 18   Minimum vertical run / maximum horizontal run.
Wall Opening
(DVT44) X = 7’3¹⁄₄” (2216 mm) 
(DVT38) X = 6’9⁷⁄₈” (2080 mm)