EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
66
All of the NvName values that are stored in EEPROM memory 
have a prefix of nci.
NOTE:
These parameters are stored in EEPROM and are 
limited to 10,000 writes. Do NOT use them as 
outputs from Control Strategies,Time Programs, or 
Switching Tables. If these points are changed more 
than 10,000 times, irreversible hardware failure 
results
Tables 20 through 28 provide point attributes as follows:
Engineering
Units—
This field indicates the point valid range and 
displayed Engineering Unit. For digital points, 
the valid states and the corresponding 
enumerated values are shown.
Default—
The value or state of the point on controller 
start-up.
E-Vision
(M) Monitor— These points are viewable within the E-Vision 
Controller Monitoring on-line screen.
(P) Parameter—These points refer to control parameters 
settable in the Application Selection dialog 
boxes in E-Vision.
(S) Schematic—These points appear in E-Vision monitor 
mode graphics.
Shareable— These points can be set up for data sharing in 
Command Multiple Points, Read Multiple 
Points, or Refer Excel 10 Points as either a 
data source or a destination.
Mappable— These points can be converted into a C-Bus 
point used by C-Bus devices. A mappable point 
has a one-to-one relationship with a C-Bus 
User Address.
Direct
 Access—
These points are accessible through the 
Subsystem Points mechanism in XBS.
Hardware
Config.—
These are points that involve controller I/O 
configuration. Any change to Hardware Config. 
points causes the W7750 to perform an 
application reset; therefore, these points can 
only be modified off-line.
Manual
Config.—
These points are used to set the controller 
outputs when in manual mode. The W7750 is 
placed in manual mode through a menu 
selection in the E-Vision Controller Monitor 
screen.
Test—
These points can be controlled in E-Visions test 
mode that is used for field checkout/ debuging.
Failure Detect
 Input Point— These points need an update periodically or a 
communication alarm is generated. The failure 
detect mechanism is only active when the NV is 
bound (bindings are configured using Refer 
Excel 10 points). The time between the updates 
is user settable.
Non-Failure Detect
 Input Point— These points (which are NVs that are bound or 
unbound) do not check for an update 
periodically and do not generate an alarm. 
NOTES:
1. Mapped points can be viewed and changed, if 
needed, on the XI581, XI582 and XI584 C-Bus 
devices and on an XBS central and on E-Vision.
2.  All Excel 10 points, mappable and calibration, 
configuration and internal data sharing points, can 
be viewed and changed, as allowed, via Direct 
Access (DA) mode in the XBS subsystem menu 
or via XI584.