Table 20. Input/Output Points.
User Address
NvName
Field Name
Engineering Units: English 
(Metric) or States plus Range
Di
gita
l S
tate
 or
 V
alu
e o
f St
ate
Default
E
-Vi
sion
 (M
, P
, S)
Sh
a
re
Map
 D
irect 
Access
H
a
rd
ware C
o
n
fig.
M
anu
al
 Co
nf
ig
.
T
est
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic
Comments
CORMode
nciIoSelect
CorOnMode
COR_ON_HEAT
COR_ON_COOL
0
1
COR_ON_COOL
P
X
CorOnMode specifies the mode when the Change Over Relay (COR) is 
energized.
nciIoSelect
ResistiveIn[0]
DISCHARGE_TEMP_PT3000
OUTDOOR_TEMP_PT3000
RETURN_TEMP_PT3000
DISCHARGE_TEMP_20KNTC
RETURN_TEMP_20KNTC
UNUSED_RAI
0
1
2
3
4
255
UNUSED_RAI
X
ResistiveIn[0] specifies which logical sensor is assigned to each physical 
analog input sensor channel according to the enumerated list that is shown 
in the Engineering Units/States column. ResistiveIn[0] is the only input 
available in the W7750A controller.
nciIoSelect
ResistiveIn[1]
DISCHARGE_TEMP_PT3000
OUTDOOR_TEMP_PT3000
RETURN_TEMP_PT3000
DISCHARGE_TEMP_20KNTC
RETURN_TEMP_20KNTC
UNUSED_RAI
0
1
2
3
4
255
UNUSED_RAI
X
ResistiveIn[1] specifies which logical sensor is assigned to each physical 
analog input sensor channel according to the enumerated list that is shown 
in the Engineering Units/States column. ResistiveIn[0] is the only input 
available in the W7750A controller.
nciIoSelect
VoltageIn[0]
RTN_HUM_C7600C
RETURN_ENTHALPY
OD_HUM_C7600C
OUTDOOR_ENTHALPY
FILTER_STATIC_PRESS_DIFF
SPACE_CO2
MONITOR_SENSOR1
RTN_HUM_C7600B
OD_HUM_C7600B
UNUSED_VAI
0
1
2
3
4
5
6
7
8
255
UNUSED_VAI
X
VoltageIn[0] specifies which logical sensor is assigned to each physical 
analog input sensor channel according to the enumerated list that is shown 
in the Engineering Units/States column. (Voltage inputs are not available in 
the W7750A controller.)
nciIoSelect
VoltageIn[1]
RTN_HUM_C7600C
RETURN_ENTHALPY
OD_HUM_C7600C
OUTDOOR_ENTHALPY
FILTER_STATIC_PRESS_DIFF
SPACE_CO2
MONITOR_SENSOR1
RTN_HUM_C7600B
OD_HUM_C7600B
UNUSED_VAI
0
1
2
3
4
5
6
7
8
255
UNUSED_VAI
X
VoltageIn[1] specifies which logical sensor is assigned to each physical 
analog input sensor channel according to the enumerated list that is shown 
in the Engineering Units/States column. (Voltage inputs are not available in 
the W7750A controller.)
nciIoSelect
DigitalIn[0]
OCC_SENSOR
OCC_TIME_CLOCK
PROOF_AIR_FLOW
ECON_ENABLE
IAQ_OVERRIDE
SMOKE_MONITOR
DIRTY_FILTER
SHUT_DOWN
WINDOW_OPEN
MONITOR
SCHED_MASTER
UNUSED_DI
2
3
4
5
6
7
8
9
10
11
12
255
OCC_TIME_CLOCK_IN
X
DigitalIn[0] specifies which logical switch type is connected to the flexible 
digital input switch channel according to the enumerated list that is shown in 
the Engineering Units/States column. DigitalIn[0] and DigitalIn[1] are the 
only inputs available in the W7750A controller. The controller is configured 
at the factory with this user address configured to OCC_TIME_CLOCK_IN.