Honeywell UV Treatment System (UV100) 제품 데이터시트

다운로드
페이지 16
UV100E ULTRAVIOLET SYSTEMS
3
68-0262—06
Temperature Ratings:
Ambient Temperature Range: 30°F to 104°F (-2°C to 40°C).
Bulb Temperature Range (In Moving Air): 30°F to 140°F 
(-2°C to 60°C).
Relative Humidity: 
Up to 95% rh, non-condensing.
Dimensions:
See Fig. 3.
Approvals:
Underwriters Laboratories: File no. E223009
The health aspects associated with the use of this product and 
its ability to aid in disinfection of environmental air have not 
been investigated by UL.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.
2. Check the rating given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
WARNING
UV Light Hazard. 
Harmful to bare skin and eyes. 
Can cause temporary or permanent loss of vision.
View illumination only through lamp light indicator on 
lamp handle.
To prevent exposure to ultraviolet light, disconnect 
power to ultraviolet system before servicing any part of 
heating and air conditioning system.
Do not mount device in location that allows ultraviolet 
light to be seen after installation.
Do not attempt to bypass duct mount switch.
CAUTION
Personal Injury Hazard. 
Power supply can cause electrical shock.
Disconnect power supply before beginning installation. 
Do not open base unit or lamp handle; there are no 
user-serviceable components inside.
Selecting Mounting Location
CAUTION
Equipment Damage Hazard. 
Ultraviolet light can cause color shift or structural 
degradation of plastic HVAC materials.
Select mounting location that prevents exposure to 
plastic components with unknown resistance to 
ultraviolet light. Three-feet minimum is recommended 
between ultraviolet lamp and plastic-fabricated devices 
(such as humidifiers and non-fiberglass media filters).
Depending on installation location, the UV System can operate 
as an Air Treatment System or as a Surface Treatment 
System.
Air Treatment System
Installed in the return air duct, the Air Treatment System kills a 
high percentage of airborne germs circulating through the 
forced air heating and cooling system. Individual results 
depend on careful installation and maintenance and on the 
actual amount of time the system fan operates. See Fig.1.
Fig. 1. Typical Air Treatment System installations.
M22857
WARNIN
G/AVER
TISSEM
ENT
!
Nocifs p
our la p
eau nue 
et les 
Veuillez lire 
et bien com
prendre 
l’install
ation et
 la maint
enance.
WARNIN
G/AVERT
ISSEMEN
T
!
Nocifs p
our la
 peau nue 
et les 
Veuillez 
lire et
 bien com
prendre 
l’instal
lation et
 la maint
enance.