UV100E ULTRAVIOLET SYSTEMS
68-0262—06
4
Surface Treatment System
When installed next to the cooling coil, the Surface Treatment 
System prevents a high percentage of the growth of 
micro-organisms such as mold that may grow on duct 
surfaces, coils and drain pans. Individual results depend on 
careful installation and maintenance. See. Fig. 2. 
Fig. 2. Typical Surface Treatment installations.
IMPORTANT
If mounting options are limited, protect plastic or 
rubber materials listed in CAUTION with ultraviolet-
resistant material such as aluminum foil duct tape.
NOTE: When the installer is uncertain about whether the drip 
pan in the installation can tolerate UV exposure, 
consult the UV exposure white paper, form no. 
50-8788, at hbctechlit.honeywell.com Web site.
1. Choose a location that is readily accessible for regular 
inspection and cleaning. Fig. 1 and 2 and show possible 
mounting locations.
2. Allow clearance in front of the device for removing the 
lamp assemblies. Fig. 3 shows lamp assembly lengths.
3. Be sure depth can accommodate full length of UV lamp 
for your model as shown in Fig. 3.
4. Be sure duct mounting location is 8 in. wide minimum.
5. Be sure 120 Vac electrical outlet is within range of unit to 
plug in the power cord.
6. Select single-lamp and dual-lamp air treatment system 
location on HVAC return air duct that is easily accessible 
with a flat mounting surface. Select surface treatment 
system location on HVAC supply air duct that is easily 
accessible with a flat mounting surface; locate the unit so 
the lamp can surround the evaporator coil and drip pan 
with ultraviolet light.
7. Mount to allow correct operation:
a. Do not mount upside down.
b. Do not mount with lamps facing up.
CAUTION
Sharp Edges Hazard.
Can cause personal injury.
Be careful when inserting ultraviolet device into sheet 
metal cutout.
Wear protective gloves when working near sheet metal.
Duct Mounting
Use the following instructions to mount the UV System on the 
air duct of an HVAC system:
1. Disconnect power to the HVAC system before installing 
the UV System.
2. Select the appropriate template for your model (see Fig. 
18-20).
3. Place the appropriate template for your model on the 
duct surface, centering the bulb hole(s) on the duct. 
4. Mark the location on the duct for 2 in. diameter bulb 
hole(s), unit mounting-screw pilot holes, and when 
installing a return air model, the 1-1/2 in. airflow sensor 
hole.
5. Cut 2 in. bulb hole(s) and 1-1/2 in. airflow sensor hole in 
the duct. Remove any burrs. Note that the airflow sensor 
protrudes out of backside of device. Be careful to avoid 
scratching or damaging the airflow sensor.
6. Use a 3/32 in. drill for pilot holes for mounting screws.
7. Be sure duct surface is flat after all holes are drilled.
8. Position entire base unit on duct. Be sure bulb and 
airflow sensor holes in duct align with unit holes. Be 
careful to avoid scratching or damaging the airflow 
sensor.
9. Install unit into duct using three (or two, depending on 
model) no.10, 2 in. Phillips head sheet metal mounting 
screws provided. (A spare screw is provided for three-
screw model.)
10. Tighten screws to 12 to 14 in.-lb so space between case 
and duct is sealed.
M22859
WARNIN
G/AVER
TISSEM
ENT
!
Nocifs pour 
la peau 
nue et l
es 
Veuille
z lire e
t bien
 comp
rendre
 
l’insta
llation
 et la m
ainten
ance.
WARNING/
AVERTI
SSEM
ENT
!
Nocifs p
our la
 peau
 nue et
 les 
Veuille
z lire et bie
n compr
endre 
l’instal
lation et
 la ma
intenanc
e.