HP Data Center Environmental Edge sensor and networking devices use 802.15.4 based radios that
operate in the 2.4 GHz industrial and scientific and medical (ISM) unlicensed band. The HP Data Center
Environmental Edge wireless communications low bandwidth will not interfere with other wireless
communications. The HP Data Center Environmental Edge wireless communications uses a mesh
network topology to transfer information.
HP Data Center Environmental Edge wireless systems achieve security at multiple levels: First HP Data
Center Environmental Edge wireless communications are not IP-enabled; they therefore are not
susceptible to external IP-based passive and active attacks. Second, HP Data Center Environmental Edge
network stack uses 128bit-AES cryptograph to provide authentication and data encryption, thereby
providing security against rogue admissions and snooping.
HP Data Center
HP Data Center
HP Data Center
HP Data Center
Environmental Edge
Environmental Edge
Environmental Edge
Environmental Edge
Server
Server
Server
Server
At the centre of the solution is the HP Data Center Environmental Edge Server. This is a HP ProLiant
DL180 G6 running Microsoft Windows Server 2008, HP Insight Environmental Observer software
components.
NOTE:
NOTE:
NOTE:
NOTE: One server can support multiple HP Data Center Environmental Edge data center locations.
HP Insight Environmental
HP Insight Environmental
HP Insight Environmental
HP Insight Environmental
Observer S/W
Observer S/W
Observer S/W
Observer S/W
HP Insight Environmental Observer S/W key features include: data center environmental visualization;
metrics tracking, alarming and historical information, including 1 year of 24x7 Technical Support and
Updates.
HP Data Center
HP Data Center
HP Data Center
HP Data Center
Environmental Edge
Environmental Edge
Environmental Edge
Environmental Edge
Environmental Base
Environmental Base
Environmental Base
Environmental Base
Station
Station
Station
Station
HP Data Center Environmental Edge Environmental Base Stations are attached to individual racks or
CRAH units and collect temperature and humidity data. The HP Data Center Environmental Edge
Environmental Base Station is battery powered and reports temperature and humidity information either
once every minute or up to once every 5 minutes based on user desired preferences. Environmental Base
Stations are simple to mount or attach within the data center environment with a couple of different
Mounting Options techniques, and include a one year parts only warranty (excluding batteries).
Server Racks
Server Racks
Server Racks
Server Racks
Environmental Base stations will be combined with the HP Data Center Environmental Edge Rack
Sensor Array
Environmental Base Stations and Rack Sensor Array can be mounted either inside the rack on
outside the rack. The Rack Sensor Array is mounted down the center of both the front and rear of
the rack
The minimum recommended configuration is to install the base stations once every third rack.
Customers can install the base station on every other rack or every rack for increased granularity
of data
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
One Environmental Base Station and the Plenum Rated Sensor Array will be installed in each
CRAH unit
Environmental Base Stations do not require the customers' CRAH/CRAC units to be modified
Other Locations
Other Locations
Other Locations
Other Locations
Environmental Base Stations can be located anywhere that the customers wants to gain insight into
a specific locations' temperature and humidity
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental Observer
Environmental Observer
Environmental Observer
Standard Features
DA - 13392   Worldwide — Version 2 — November 16, 2009