Specifications
Table 3 lists the specifications for the three 3000VA UPS models.
Table 3. Specifications (Part 1 of 2)
Specification
IBM 3000VA LCD 3U Rack
UPS (100V/120V)
IBM 3000VA LCD 3U Rack
UPS (200V/208V)
IBM 3000VA LCD 3U Rack
UPS (230V)
IBM part number
5395-3AX
5395-3JX
5395-3KX
VA/Watts rating
2880 VA / 2700W (120V)
2300 VA / 2300W (100V)
2300 VA / 2300W (100V)
3000 VA / 2700W
3000 VA / 2700W
Nominal output voltage
(Vac)
100/120V AC
208V AC
230V AC
Load groups
Two
Two
Two
Output connections
One NEMA L5-20R
Two NEMA 5-20R
Two IEC 320 C19
Two IEC 320 C13
Two NEMA 5-20R
Two IEC 320 C19
Two IEC 320 C13
Two NEMA L6-20R
Two IEC 320 C19
Two IEC 320 C13
Two IEC 320 C19
Two IEC 320 C13
Two IEC 320 C19
Eight IEC 320 C13
Eight IEC 320 C13
Nominal output voltage
regulation
92-108V (100V)
106-132V (120V)
106-132V (120V)
184-228V (208V)
208-253V (230V)
Input
Nominal input voltage
(auto sensing at first
(auto sensing at first
power-up)
100/120V
208V
230V
Input frequency (auto
sensing)
50/60 Hz +/- 3 Hz
50/60 Hz +/- 3 Hz
50/60 Hz +/- 3 Hz
Input connection Type
NEMA L5-30P (fixed line
cord)
IEC 320-C20
IEC 320-C20
Included line (input) cords
NEMA L5-30P 2.0 m (fixed) (1) IEC 320 C19 to NEMA
L6-20P 4.3 m
(2) IEC 320 C19 to LP-3
(2) IEC 320 C19 to LP-3
4.3 m (Taiwan)
Optional country specific
line cords (See Table 2)
Input voltage range, mains
operations
84-121V for 100V
97-145V for 120V
97-145V for 120V
155-255V for 208V
160V-286V for 230V
Batteries
Typical backup times
See Table 4
See Table 5
See Table 6
Battery type
Valve Regulated Lead Acid (VRLA) – maintenance-free, sealed, leak-proof
Optional External Battery
Pack
Yes, 69Y1982
Yes, 69Y1982
Yes, 69Y1982
Typical recharge time
4 hours to 90% charge from a UPS/battery discharge of 50% rated load