Cisco IW3702 Access Point Getting Started Guide
 
Installation
Grounding the Access Point
In all installations, after mounting the access point, you must properly ground the unit before connecting power cables.
Warning:
 This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the 
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an 
electrician if you are uncertain that suitable grounding is available.
 Statement 1024
Warning:
 Installation of the equipment must comply with local and national electrical codes. Statement 1074
The access point is shipped with a grounding kit.
Figure 7
Access Point Grounding Kit Contents
Note: 
The grounding kit also includes the oxide inhibitor, which is contained in a tube.
To ground the access point:
1.
Use a crimping tool to crimp a 6-AWG ground wire (not included in the grounding kit) to the ground lug.
2.
Connect the supplied ground lug to the access point ground connection point using the supplied screws. Apply 
supplied oxide inhibitor between the ground lug and the access point ground connection.
3.
Tighten the screws to 20-25 inch-lbs of torque.
1
Grounding lug
2
Screws x 2, M4 x 6mm
300622
1
2
391287