Samsung AR12KVSPDGM 사용자 설명서
44 English
ins
tallation
tallation
Step 3.4 Adding refrigerant
If you use a pipe longer than the length specified in
the piping codes and standards, you must add 15g of
refrigerant R-410A for each extra metre. If you use a pipe
shorter than the length specified in the piping codes and
standards, the evacuating time is normal. Refer to the
Service Manual for further details.
the piping codes and standards, you must add 15g of
refrigerant R-410A for each extra metre. If you use a pipe
shorter than the length specified in the piping codes and
standards, the evacuating time is normal. Refer to the
Service Manual for further details.
CAUTION
• The remaining air in the Refrigeration cycle, which
contains moisture, may cause malfunction of the
compressor.
compressor.
• Always contact the service centre or a professional
installation agency for product installation.
R-410A is a mixed type of refrigerant. It is necessary for
recharging under conditions of liquid. When recharging
refrigerant from the refrigerant cylinder to the equipment,
take the following instructions:
Before recharging, check whether the cylinder has
a siphon or not. There are two ways to recharge the
refrigerant:
recharging under conditions of liquid. When recharging
refrigerant from the refrigerant cylinder to the equipment,
take the following instructions:
Before recharging, check whether the cylinder has
a siphon or not. There are two ways to recharge the
refrigerant:
NOTE
• If R-410A refrigerant is charged with gas, the
composition of the charged refrigerant changes and
the characteristics of the equipment vary.
the characteristics of the equipment vary.
• During the measuring operation of refrigerant quantity
added, use electronic scales. If cylinder doesn't have
siphon, upset it.
siphon, upset it.
Charge the refrigerant
standing the cylinder upright.
<Cylinder with siphon>
Charge the refrigerant
turning the cylinder upside
down.
Siphon
<Cylinder without siphon>