Samsung AR12KVSPDGM 사용자 설명서

다운로드
페이지 47
46 English
ins
tallation
in order to avoid refrigerant loss to the atmosphere. 
1.  Shut off the liquid valve with the Allen 
wrench. 
2.  Turn on the air conditioner in cooling with 
fan operating at high velocity. (Compressor 
will immediately start, provided 3 minutes 
have elapsed since the last stop.) 
3.  After 2 minutes of operation, shut the 
suction valve with the same wrench. 
4.  Turn off the air conditioner and switch 
mains supply off. 
5.  Disconnect tubing. After disconnection, 
protect valves and tubing ends from dust. 
  CAUTION
•  Compressor damage may occur if the compressor is 
run at a negative suction pressure.
Pumping down for removing the product
1.  Hold down the   (Power) button on the 
indoor unit for 5 seconds. Beep sounds 
immediately to indicate that the product is 
ready for pump down procedure. 
2.  Let the compressor run for more than 5 
minutes. 
3.  Release the valve caps on High and Low 
pressure side. 
4.  Use L-wrench to close the valve on the 
high pressure side. 
5.  After approximately 1 minute, close the 
valve on the low pressure side. 
6.  Stop operation of the air conditioner by 
pressing the   (Power) button on the 
indoor unit or remote control. 
7.  Disconnect the pipes. 
1
2
Liquid service port 
<High pressure>
Gas service port 
<Low pressure>
Off
1 minute