Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Programmed Activation by FACP
MS-9600, MS-9200UDLS and MS-9200UD
Simultaneous Activation of All Audio Zones - this is a single trip mechanism via a zone on the 
ACS/ANN-BUS link or CMD input trigger that activates all the audio zones at the same time 
(refer to the FACP specific programming sections in this Appendix.)
Fire Fighter Telephone Remote Annunciation via ACS/ANN-BUS - an intelligent FACP utiliz-
ing addressable monitor modules and the ACS/ANN-BUS link can annunciate the status of the 
remote FFT jacks (refer to the FACP specific programming section in this Appendix.)
D.1  MS-9600, MS-9200UDLS and MS-9200UD
The ACC-25/50ZS and ACC-25/50ZST can be automatically triggered via the ACS serial link by 
the MS-9600 (version 2 or higher), MS-9200UDLS and MS-9200UD (version 2 or higher) to trans-
mit one of five messages over selected speaker circuits.  This is accomplished by zone program-
ming at the FACP.
Annunciation of remote Fire Fighter Telephone locations on the ACC-FFT keypad (ACC-
25/50ZST only) is also transmitted via the ACS serial link.  This is accomplished by point pro-
gramming at the FACP.
D.1.1  Overview
The ACC-25/50ZS and ACC-25/50ZST provide 8 speaker circuits standard via the ACC-ZSM 
Zone Splitter Module.  Expansion to 24 speaker circuits is possible by adding ACC-25/50DAZS 
panels.  The ACC-25/50ZS and ACC-25/50ZST also have the ability to generate and direct one of 
five messages to specific speaker circuits.
The MS-9600, MS-9200UDLS, and MS-9200UD communicate with the ACC-25/50ZS and ACC-
25/50ZST over the ACS annunciator terminals.  The ACS Annunciator option for ACS address 01 
must therefore be enabled in the FACP programming.  When this option is enabled, FACP zones 
Z33 through Z56 are dedicated as output zones for speaker circuits 1 through 24 respectively.  
FACP Zone 32 is dedicated to turn on all speaker circuits.  The FACPs will then allow the installer 
to program individual addressable devices to any of the speaker circuits using the Zone Setup 
menu.  In addition, one of five messages can be generated over the selected speaker circuit.
To annunciate remote Fire Fighter locations in the ACC-25/50ZST, ACS address 07 must be 
enabled in the MS-9200UDLS or address 05 for version 4 or higher; or ACS address 07 for the MS-
9600.  When this option is enabled, SLC points 75-98 on the MS-9200UDLS or SLC points 135-
158 on loop #1 of the MS-9600 are dedicated to FFT 1-24 indicators on the ACC-FFT keypad. 
All faults on the ACC-25/50ZS and ACC-25/50ZST are sent upstream via the ACS link to the MS-
9600, MS-9200UDLS, or MS-9200UD and are indicated as an ACS Fault on the display.
Important Notes: 
1. For proper operation, a message must be assigned to each zone that is programmed to activate 
an audio speaker circuit.
2. The message repeat setting on the ACC-25/50ZS and ACC-25/50ZST should be set to infinite.  
This will ensure that lower priority activated zones will continue to broadcast the voice 
message.
3. CMD inputs are not used for activation of the ACC-25/50ZS and ACC-25/50ZST, however, 
4.7K
 ELRs must still be connected across CMD3, CMD4, and CMD5.
4. When implementing annunciation of remote FFT locations, the ACC-25/50ZST defaults to 
receive only mode for ACS address 05 or ACS address 07.
D.1.2  Basic MS-9600/MS-9200UD/MS-9200UDLS & ACC-25/50ZS/T 
Step-By-Step Install/Setup
1. Connect ACS wiring from FACP to ACC-25/50ZS or ACC-25/50ZST.
2. Set ACS Address Wheels on ACC-ZPMK to address 01.