Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Programmed Activation by FACP
MS-9600, MS-9200UDLS and MS-9200UD
D.1.4  ACC-25/50ZS and ACC-25/50ZST Switch Settings
ACC-ZPMK DIP Switch S1
Switches 1, 2, and 3 are used to configure the ACC-25/50ZS and ACC-25/50ZST for operation 
with a specific FACP as shown in the following table:
Switch 4 - future use
Switches 5, 6, 7, and 8 - used to set the number of ACC-25/50DAZS panels installed. 
ACC-ZPMK Rotary Address Switches S2 and S3
ACS Protocol:
The address switches must be set to ACS address 01 to communicate with the FACP.  Any other 
ACS devices which are set to address 01 should be in Receive Mode only.
S2=1
S3=0
ANN-BUS Protocol:
The address switches can be set to any address between 01 through 08 to communicate with the 
FACP.  Any other ANN-BUS devices must be set to a different address.
S2=1-8
S3=0
ACC-ZSM Zone Splitter Module Switch Settings
ACC-FFT Fire Fighter Module Switch Setting (ACC-25/50ZST only)
SWITCH
1
SWITCH
2
SWITCH
3
CONFIGURED FOR OPERATION WITH FOLLOWING FIRE ALARM 
CONTROL PANEL
OFF
OFF
OFF
MS-9200UD version 1
OFF
ON
ON
ACS Protocol: MS-9600 version 1
ON
OFF
OFF
ACS Protocol: MS-9600 version 2 or higher
ON
OFF
ON
ACS Protocol: MS-9200UDLS or MS-9200UD version 2 or higher
ON
ON
OFF
ANN-BUS Protocol:
MS-9600LS Version 4 or higher
MS-9200UDLS Version 4 or higher
Table D.2  FACP Configuration
S1 DIP Switch
ON
OFF
5
                                                               not used (must be set to OFF)
6
This switch works in conjunction with switches 7 & 8 to set the number of ACC-25/50DAZS panels connected  
7
This switch works in conjunction with switches 6 & 8 to set the number of ACC-25/50DAZS panels connected  
8
6 OFF, 7 OFF, 8 OFF = No ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 OFF, 7 OFF, 8 ON = 1 ACC-25/50DAZS Distributed Audio Panel connected to ACC-25/50ZS/T
6 OFF, 7 ON, 8 OFF = 2 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 OFF, 7 ON, 8 ON = 3 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 ON, 7 OFF, 8 OFF = 4 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 ON, 7 OFF, 8 ON = 5 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
Table D.3  Number of ACC-25/50DAZS Panels Installed