eaton corporation ePDU Industrial Products Catalog
8
Single-Phase Systems-North American TPC115-10 Series
120V~ OR 240V~, 15A, 20A and 30A, 50/60 Hz
RACK MOUNTED
•  19” x 1.72” (1U) x 8.0”
•  Approximate shipping weight: 14 lb.
(10) NEMA OUTLETS
•  2 unswitched on front and 8 switched  
 on rear panel. Unswitched outlets are  
 tied to the SW-II outlet section
POWER INPUT
•  Power cable with plug is attached to unit
 through the rear panel cable grip
(3) INDICATOR LIGHTS
•  Main breaker power “on” and power to
 the unswitched outlets
•  Power “on” to the SW-I outlets
•  Power “on” to the SW-II outlets
SPIKE/SURGE SUPPRESSION
•  L-N, L-G, N-G
•  Refer to Chart 1 on page 20
EMI/RFI FILTERING
•  Common mode line to ground
•  Differential mode line to line
•  Refer to Chart 4 (15A/20A units) and  
 Chart 5 (30A units) on page 20
OVERLOAD CIRCUIT PROTECTION
•  Electromagnetic breaker
 provides manual on/off switching and  
 trips in an overload condition
LOCAL/OFF/REMOTE SWITCHING
•  Local: Power “on or off” to the switched
 outlets
•  Off: When breaker is “on” but this switch
 is in the “off” mode, you will have power
 to the unswitched outlets only
•  Remote: Power “on or off” to the
 switched outlets via a remote device
•  Latching remote, on “LT” systems, has  
 the selection switch wired for
 Remote/Off/Remote - There is no local
 control
MULTIPLE TIME DELAY™ (MTD™)
•  Activated “locally” or “remotely”,
 SW-I outlets power up immediately,
 followed four seconds later by
 SW-II outlets which is followed four  
 seconds later by the sequenced remote
 I/O port.
•  Add “/MTD” after part number, i.e.
 TPC115-10-A/MTD
REMOTE I/O PORTS
•  3 front/2 rear (see page 16)
•  Remote on/off and EPO control, EPO  
 overrides remote and local control
•  Sequence Power Up additional
 equipment down line (3rd connector on
 front panel)
•  Latching remote feature - (N/C) EPO,  
 momentary start
–  Add “-LT” to the part number when
 the MTD feature is not being used
–  Add “/LT” to the part number
when the MTD feature is used
SPECIFICATIONS
TPC115-10-A
TPC115-10-A2
TPC115-10-B
TPC115-10-C
TPC115-10-D
TPC115-10-F
Approvals
UL/cUL
UL/cUL
UL/cUL
UL/cUL
UL/cUL
UL/cUL
Voltage Input/Output (50/60 Hz)
120V~
120V~
240V~
120V~
120V~
240V~
Current Input
15A
20A
15A
30A
30A
30A
Current Output
12A
16A
12A
24A
24A
24A
Full Load VA
1440 VA
1920 VA
2880 VA
2880 VA
2880 VA
5760 VA
NEMA Outlets
5-15R
5-20R
6-15R
5-15R
5-20R
6-15R
Circuit Breaker with Kick Guard
15A
20A
15/15A
15/15A
15/15A
(2) 15/15A 
EMI/RFI Filter
20A
20A
20A
30A
30A
30A
Multi-Stage Surge Suppression
270V/150V
270V/150V
320V/270V
270V/150V
270V/150V
320V/270V
Power Cord/Length
14/3, 9’
12/3, 9’
14/3, 9’
10/3, 15’
10/3, 15’
10/3, 15’
NEMA Power Input Plug
5-15P
5-20P
N/A
L5-30P
L5-30P
L6-30P
RCP100-GRY
KIT-CABLRES-08
Optional Cable Restraint System (refer to page 19)
Optional Accessories Available
Remote Control Panel (refer to pages 16-17)
TPC115-10-D Front
TPC115-10-D Rear