Eaton KIT-CABLRES-24 사용자 설명서

다운로드
페이지 23
www.epdu.com 1.800.356.5794
7
CHASSIS
•  19” x 1.72” (1U) x 9.5”
•  Weight approximately 12 lb.
•  Detachable mounting brackets allow for
 several mounting options
NEMA or IEC 320 OUTLETS
•  IPC3401 has 8 IEC 60320 Type C13
 –  Rated by UL/CSA 125V~/15A
 –  Rated by UL/CSA/VDE 250V~/10A
•  IPC3402 has 8 NEMA 5-15R
•  IPC3402-A2 has 8 NEMA 5-20R
•  IPC3402-2756 has 4 NEMA 5-20R and
 4 NEMA 5-15R
•  IPC3402-2930 has 8 NEMA 5-15R
(11) INDICATOR LIGHTS
•  Main power to system-CB “on”
•  Individual power “on” to outlets 1-8
•  Data acquisition and remote disable
REMOTE or LOCAL CONTROL
•  Serial RS232 port (DB9 Male) for direct
 computer or modem connection
•  RS485 input/output for strapping up to
 10 systems together over CAT.5 cable
•  Local: one on/off switch for each outlet
•  -NET SYSTEMS ONLY: RJ45 for
 network connections (Ethernet)
REMOTE DISABLE
•  With the push of a button, disable
 remote access to the IPC when needed
POWER SUPPLY
•  The IPC3401 series features a full
 range power supply for operation at
 100-240 Vac input/output
BAUD RATE
•  Default: 9600 baud
EMI/RFI FILTERING
•  Common Mode - Line to Ground
•  Differential Mode - Line to Line
•  Filtered inlet isolates noise before
 entering the system
•  Refer to chart 3 on page 20
•  IPC3402-2756 and IPC3402-2930
 do not have filtering
SPIKE/SURGE SUPPRESSION (TVSS)
•  Line to Line
•  Refer to chart 1 on page 20
•  Multi-stage, both MOVs and SAPs
BRANCH CIRCUIT PROTECTION
•  UL498 Listed Main Disconnect Breaker
 and guard, with a long time delay curve
 provides manual on/off switching and
 trips in an overload condition
POWER INPUT
•  IEC 60320 Type C20 EMI/RFI Filtered Inlet
•  Mating power cables must be ordered
 separately (page 18)
•  IPC3402-2756: attached 10’ cable and
 NEMA L5-30P
OUTLET STATUS
•  Query the IPC for Outlet and Watch Dog
 status, i.e. outlets are “on” or “off”
STRAPPING
•  Strapping allows up to 10 IPCs
 (80 outlets) to be controlled at one address
•  Units are connected together via the
 RS485 “IN” and “OUT” connectors
UNIT NAME / PASSWORD
•  The IPC comes with a default name
 @@@@, which can be changed to
 any four alphanumeric characters
•  Optional 3 character password
MULTIPLE TIME DELAY (MTD)
•  Sequence power up and power down to
 outlets with a one second time delay
 (factory set)
•  User Programmable:
 –  Set power “on” sequence to any
   combination of outlets
 –  Set the MTD
timing from 1 second
   to 999 seconds, i.e. 009 = 9 seconds
AUTO-EVENT COMMAND RESPONSE
•  The IPC will automatically update the status
 of outlets (“on” or “off”) via serial or telnet
SOFTWARE CONTROLS
•  Multi-platform compatible
•  Control via Terminal Emulation Software
•  Web interface for browser control
COMMANDS AVAILABLE
•  All outlets on/off
•  Specific outlets on/off
•  Set up and sequence on/off all outlets
•  Create password and unit address
•  Outlet naming (8 characters)
•  Set up, enable or disable Watchdog
•  Display outlet and Watchdog Timer status
•  Automatically receive update outlet
 status whenever there’s a change
•  Auto-reboot outlet 1 with a five-second
 delay on restart
SPECIFICATIONS:
IPC3401
IPC3401-NET
IPC3402
IPC3402-NET
IPC3402-A2
IPC3402-A2-NET
IPC3402-2756
IPC3402-2930
Approvals
UL/cUL, CE, GS, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL
UL/cUL
Voltage (50/60Hz)
100-240V~
100-240V~
120V~
120V~
120V~
120V~
120V~
120V~
Current Input
20A @ 120V~  
16A @ 240V~
20A @ 120V~  
16A @ 240V~
20A
20A
20A
20A
30A
30A
Current Output
16A
16A
16A
16A
16A
16A
24A
24A
Full Load VA
1920 VA @ 120V~ 
3840 VA @ 240V~
1920 VA @ 120V~  
3840 VA @ 240V~
1920 VA
1920 VA
1920 VA
1920 VA
2880 VA
2880 VA
Outlets (IEC or NEMA)  Type C13
Type C13
5-15R
5-15R
5-20R
5-20R
(4) 5-20R, (4) 5-15R (8) 5-15R
Circuit Breaker
20/20A
20/20A
20A
20A
20A
20A
20/10A
20/10A
EMI/RFI Filter
20A
20A
20A
20A
20A
20A
N/A
N/A
Surge Suppression
270V
270V
270V
270V
270V
270V
270V
270V
Power Input
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
L5-30P
L5-30P
Power Cord
Power cables must be ordered separately. Refer to page 18 for power cable options.
10/3AWG 10’
10/3AWG 10’
Ethernet Control
NO
YES
NO
YES
NO
YES
YES
YES
Serial Control (RS232) YES
YES
YES
YES
YES
YES
YES
YES
Please refer to page 18 for power cable assemblies to match your country specific requirements.
Intelligent Power Control